Adjustment ETM
Empty adjustment - Active surface free
When the adjustment with the product to be detected is not possible, an empty adjustment can be made,
e. g. the product to be detected is not known at the first commissioning of the probe / sensor adjustment,
but an overfilling must be excluded. When the level is filled for the first time, we recommend making a full
adjustment so that an optimal adjustment is made with the probe / sensor for the material to be detected.
• The active area of the probe / active surface of the sensor is free.
• Hold the teach magnet on the teachspot for approx. 5 seconds until the LED flashes green.
• Remove Teach-Magnet.
• During the initialization process the LED is flashing green with higher frequency.
The empty adjustment is finished when the LED is static green. With this adjustment the probe / sensor
has the largest sensing distance that is possible at the current mounting position. The switching hysteresis
is calculated automatically.
Full adjustment - Active surface covered
• The active area of the probe / active surface of the sensor must be covered completely with the product
to be detected or the product must be in the desired position.
• Hold the teach magnet on the teachspot for approx. 10 seconds until the LED flashes yellow.
• Remove Teach-Magnet.
• During the initialization process the LED is flashing yellow with a high frequency
The full adjustment is finished when the LED is static yellow and A1 is high. The probe / sensor is
now optimally adjusted for the detection of the media currently being used and the current mounting
conditions. The switching hysteresis is calculated automatically.
Factory reset
For the factory reset, please do the following steps:
• Hold the teach magnet on the teachspot for approx. 15 seconds until the LED flashes green with
double pulses.
• Remove Teach-Magnet.
The evaluation unit is back in delivery condition.
Test function
The test function can be used to check the connection between the evaluation unit with the control
panel.
• Hold the teach magnet on the teachspot until the LED flashes green and yellow (approx. 20 seconds).
Output A1 and A2 are clocking simultaneous with ca. 0.5 Hz.
The test function is activated until you remove the Teach-Magnet.

Maintenance, repair, disposal

• Maintenance for this device is not necessary when used as intended.
• It is not possible to repair the device. If you have any problems, please contact directly your customer service.
• Please dispose of the device in a way that is environmentally friendly according to the national regulations.