Eopus
P10: Proportional band (P). It can be adjusted from %1.0 to %100.0
(Default: 10.0).
P11: Output Control Period. If control output is SSR, it can be adjusted
from 0.5 to 150.0 seconds. If control output is Relay, it can be adjusted
60.0 to 150.0 seconds. (SSR Default: 10.0; Relay Default: 60.0).
P12: Proportional Offset value. This parameter is used for shifting the
proportional band. It can be adjusted from (-Operation Scale Maximum
/2) to (Operation Scale Maximum /2)
P13: Integral Time. It can be adjusted from 0 to 3600 seconds (Default:
100).
P14: Derivative Time. It can be adjusted from 0.0 to 999.9 seconds
(Default: 25.0).
P15: If tune parameter is set to SELF or Auto, device starts to calculate
PID parameters automatically. (Default: no)
0 No: Device does not calculate PID parameters.
1 Self: Step Response Tuning operation.
2 Auto: Limit Cycle Tuning operation.
P16:
Minimum temperature to off the burner.
P17: Timer displayed form. If parameter value set as 0, timer form is
Minute-Second. If parameter value set as1, timer form is Hour-Minute.
P18: Timer counts direction parameter. If the parameter set as 0, timer
counts downt-to-up. If the parameter set as 1, timer counts up-to-down.
P19:
time to turn on the light before the end of the process, it is used as
alert. (min)
P20:
Time when the light turns off after being pressed. (seconds)
CH-02-N
P21:
The process ended once the time has elapsed. (seconds)
P22: Buzzer active time parameter. If parameter value set as **** /,
Buzzer will be active continuously. If parameter value set as a different
value (from 1 to 9999 seconds), Buzzer will be active during the entered
time.
P23: Digital input circuit parameter. If the parameter set as 0, circuit is
Normally Open (NO). If the parameter set as 1, circuit is Normally
Closed (NC).
P24: Type of command when digital input activated. If the parameter set
as 0, timer stops counting and resets time. If the parameter set as 1, timer
pauses counting.
P25: If the Steam Duration Parameter is selected as 0 then the steam
output will be on during the Steam button is pressed. If the parameter
value set as a different value (from 1 to 9999 seconds), after pressing the
steam button, output will be on during the Steam Duration Parameter
value. If Steam button is pressed when steam output is on, steam output
will be off.
P26: Password for accessing to the parameters section. It can be adjusted
from 0 to 9999. If parameter value is 0, password screen is not seen. If
parameter value is different from 0 and;
If user enters different value from saved value, device
will return to main screen automatically.
P27:
Time for the screen to turn off if there is no default user activity
P28: Minimum steam operating temperature.
Innovation in Control