Information (reading only)
Level 1
Level 2
Description
InI
Option chosen in the configuration wizard
Pump down active? 0=No, 1=Yes
Pd**
PU
Program version
Pr
Program revision
tid
bU
Bootloader version
br
Bootloader revision
PAr
Parameter map revision
EP
Exit to level 1
** It can only be modified using the configuration wizard (InI).
Messages
Messages
Pd
Pump down malfunction error (Shutdown)
LP
Pump down malfunction error (Start-up)
E1/E2/E3
Probe 1/2/3 failure (Open circuit, crossed circuit or temperature outside the limits of the probe)
Ad0
Open door alarm. Only if the door stays open for a greater time than is indicated in parameter A12
AH
Maximum temperature alarm in control probe. The temperature value programmed in A1 has been reached
AL
Minimum temperature alarm in control probe. The temperature value programmed in A2 has been reached
AE
External alarm activated (by digital input)
AES
Severe external alarm activated (by digital input)
Adt
Defrost alarm concluded due to time-out. The time established in d1 has been exceeded
HACCP alarm. The temperature has reached the value of parameter h1 during a longer period than has been
HCP
established in h2
HACCP alarm due to a fault in the power supply. The temperature established in h1 has been reached following a
hCP + PF
fault in the power supply
dEF
Indicates that a defrost is being performed
PAS
Access code (Password) request. See parameters b10 and PAS
Shown sequentially with the temperature: The controller is in demo mode, the configuration has not been
S1 - S2
made.
A: Activates the acoustic alarm
R: Activates the alarm relay
© Danfoss | DCS (vt) | 2021.02
Values
Min.
Def.
A
AN36292867744601-000101 | 7
Max.
R