Siemens REV34 Serie Instrucciones De Montaje página 6

Ocultar thumbs Ver también para REV34 Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 18
Mounting notes REV34..
DE
1
Placement of unit
EN
·
The REV34.. should be mounted in the main living room (for wall
mounting, refer to Figs. B through E)
FR
·
The REV34.. must be located such that it can acquire the room
temperature as accurately as possible, without getting affected by
direct solar radiation or other heat or refrigeration sources
IT
NL
ES
PT
CS
HU
Commissioning
PL
1
Switching on the REV34..
(also refer to operating instructions and Fig. F)
SV
1.1 Removing the battery transit tab
FI
·
As soon as the black battery transit tab is removed, the unit is ready
to operate and runs through a 180-second initialization phase. During
this phase, the actuator is driven to the fully closed position
DA
Important: The actuator requires maximum 150 seconds for traveling to
the fully closed position.
TR
The controller must be refitted to its baseplate within 30 seconds!
EL
Configuration and function check REV34..
1
Configuration
1.1
DIP switches
ON /
Sensor calibration on
See
1.1.1
Sensor calibration off
Setpoint limitation
16...35 °C
1.1.2
Setpoint limitation
3...35 °C
Temperature display °F
1.1.3
Temperature display °C
Optimum start control: 1 h/°C
Optimum start control: ¼
h/°C
1.1.4
Optimum start control: ½
h/°C
Optimum start control: Off
1.1.8
When changing one or several DIP switch positions, a DIP switch reset must be made by pressing the DIP switch reset button (also
refer to Fig.
). Otherwise, the previous settings will be maintained!
6/50
min.
10 cm
OFF
1
2
DIP switch reset
Factory setting: All DIP switches
2
Mounting
·
Refer to Figs. A through E
3
Checking the wiring
For electrical connections, refer to "Connection diagram".
Note:
Do not use stranded wires, only solid wires
or stranded wires with ferrules!
4
Notes
·
The local regulations for electrical installations must be
complied with
·
If the reference room is equipped with thermostatic radiator
valves, they must be set to their fully open position
·
External preliminary protection with max. C 10 A circuit
breaker is required in all cases
2
Selecting the language
·
When starting up, the display shows the type of controller at top
left and "THANK YOU ..." in all available languages on the text
line
·
Press one of the buttons to stop the running display. The choice
of languages starts with "ENGLISH" (factory setting). Press
or
or move the slider to confirm the selected language (also refer to
Fig. G)
3
4
5
6
7
ON
1
2
3
4
5
6
2015-02-27
until the language you require appears. Press
8
9
10
Medium sized room
Small sized room
Large sized room
Medium sized room
Medium heating
capacity
Undersized heating
capacity
Oversized heating
capacity
Medium heating
capacity
Quartz
Radio clock
7
8
9
OFF
See
1.1.5
1.1.6
1.1.7
1.1.8
CE1G2208xx
Tabla de contenido
loading

Tabla de contenido