Installation Instructions

1. Product selection
Check kit selection with cable diameter dimensions in Table 1.
Table 1
Nominal
Kit
Cable Range
HVS-3521S
1/0-3/0 AWG
HVS-3522S
4/0-600 kcmil
HVS-3523S
600-1000 kcmil
HVS-3524S
1250-2000 kcmil
2. Check ground braid
Verify that ground braid(s) or bond wire have equivalent cross-
section to cable metallic shield. Additional braid may be needed for
lead sheath cables, or if external grounding or shield interrupting is
required.
Tyco Electronics HVS-EG supplies ground braid, spring clamp and
suggested modifications to make an external ground or shield
interrupt.
3. Prepare cables
Choose the cable type (Choice 1-3) and use the dimensions shown in
Table 2 to prepare the cables.
Table 2
Jacket
Cutback
Kit
A
HVS-3521S
14" (355mm)
HVS-3522S
17" (430mm)
HVS-3523S
18" (460mm)
HVS-3524S
18" (460mm)
If Metallic Tape Shield or Lead Sheath Cable
If Drain Wire Shield Cable
PII 53106
Revision AL
Maximum
Jacket
Diameter
1.55 (39mm)
2.10 (53mm)
2.80 (71mm)
3.0 (76mm)
Metallic Shield
Cutback
B
11" (280mm)
14" (355mm)
15" (380mm)
15" (380mm)
Choice 1
Choice 2
Insulation
Maximum Connector
Diameter
Dimensions
Range
Length
0.95-1.35 (24-34mm)
5.0 (125mm)
1.20-1.70 (30-43mm)
8.0 (200mm)
1.55-2.15 (39-55mm)
10.0 (255mm)
2.10-2.63 (53-66mm)
10.0 (255mm)
Semi-con
Maximum Connector
Cutback
Dimensions
C
Length
7-1/4" (185mm)
5.0" (125mm)
9" (230mm)
8.0" (200mm)
10" (255mm)
10.0" (255mm)
10" (255mm
10.0" (255mm)
2
Diameter
1.00 (25mm)
1.50 (38mm)
1.85 (47mm)
2.60 (66mm)
Expansion
Diameter
Gap "X"
1.00" (25mm)
1/4" (5mm)
1.50" (38mm)
1/2" (15mm)
1.85" 47mm)
1/2" (15mm)
2.60" (66mm)
1/2" (15mm)
C L
A
B
C
C L
A
C
PCN 690615-000
Effective Date: June 17, 2010