Leuze electronic PSU-10A-3P-24V-H Manual De Instrucciones página 2

Idiomas disponibles

Idiomas disponibles

13 14
13 14
OUTPUT :
OUTPUT:
24VDC / 10A
24VDC / 10A
Alarm
Alarm
13 14
13 14
OUTPUT :
OUTPUT:
24VDC / 10A
24VDC / 10A
Alarm
Alarm
OK / Alarm
OK / Alarm
Uout Adj. 24-28V
Uout Adj. 24-28V
Art. No. 50132589
Art. No. 50132589
INPUT Y 3x360-500VAC
INPUT Y 3x360-500VAC
0.75 - 0.55A
0.75 - 0.55A
50/60Hz
50/60Hz
L1
L1
L2
L2
L3
L3
3x400 VAC
PE
13
3x400 VAC
PE
14
L3
500-700 VDC
(-)
-
L2
(+)
+
L1
PE
15
(1) General
This unit employs many features previously unavailable in an industrial power supply. It has been
designed to withstand the high levels of interference found in heavy industry and has emission
levels low enough for it to be used in residential, commercial and light industrial environments.
The PSU-10A-3P-24V-H has a high level of reserve power. This enables loads with significant
inrush current to be supported and will also ensure that circuit breakers will trip in event of short
circuit.
A protective feature is provided which will take control as the unit approaches the power limit due
the overload or excessive temperature brought about by lack of ventilation.
If input voltage drops down to 3 x 300 VAC for 4 sec, output voltage still complies to PLC standard
EN 61131-2 (≥ 20,4 VDC).
Use only in star-architecture TN, TT and IT networks.
Only for use in pollution degree 2 environment (Controlled Environment).
Operating instructions
Power Supply Unit 3 PHASE
PSU-10A-3P-24V-H
Parallel mode switch
Parallel mode switch
OFF - ON
OFF - ON
Fertigungs-Code
Fertigungs-Code
Made in Czech Republic
Made in Czech Republic
potential free alarm contact
potential free alarm contact
SWITCH MODE POWER SUPPLY UNIT
SWITCH MODE POWER SUPPLY UNIT
(NO - contact 13 / 14)
(NO - contact 13 / 14)
PSU-10A-3P-24V-H
PSU-10A-3P-24V-H
ART. NO. 50132589
ART. NO. 50132589
13
13
14
14
IND.CONT.EQ.
IND.CONT.EQ.
61RM
61RM
INPUT: Y 3x360-500VAC, 50/60Hz, 0.75-0.55A
INPUT: Y 3x360-500VAC, 50/60Hz, 0.75-0.55A
Max. ratings
Max. ratings
60 V AC/DC, 80 mA, SELV
60 V AC /DC, 80 m A, SELV
OUTPUT: 24 - 28VDC, 10 - 8.6A, IP20, SELV
OUTPUT: 24 - 28VDC, 10 - 8.6A, IP20, SELV
Max. surrounding air temperature +60 C (up to +70 C with derating)
Max. surrounding air temperature +60 C (up to +70 C with derating)
o
o
o
o
Derating 7.2W / C (Ta > +60 C)
Derating 7.2W / C (Ta > +60 C)
o
o
o
o
CAUTION
CAUTION
- Read instruction manual before installation and use.
- R ead in structi on m anu al b efor e in stall ati on and u se.
- Risk of electric shock. Do not open the case.
- Ri sk of el ectri c shock. D o not op en th e case.
- N o u ser ser vi ceabl e par ts in si de.
- No user serviceable parts inside.
ATTENTION
ATTENTION
- Lir e atten ti vem en t l a noti ce d'in stall ati on avan t
- Lire attentivement la notice d'installation avant
la mise en service de l'appareil.
l a mi se en ser vi ce de l' appar eil.
- Risque d'électrocution. Ne pas ouvrir l'appareil.
- Ri squ e d' él ectr ocu ti on. N e pas ou vrir l' appar eil.
- Ne contient pas de pièces pouvant être remplacées
- N e con ti en t pas de pi èces pou van t êtr e r empl acées
par l'u tili sateur
par l'utilisateur
32
28
24
20
16
12
8
4
0
0
2
4
6
8
10
12
DC24V
DC48V
(DC +/ - 24V)
(DC +/ - 24V)
50%
100%
(2) Technical specification, Art. No. 50132589
Nominal voltage
Input voltage range
Use allowed with two phases
Nominal frequency
Input current, I
om.
Input current with two phase
Inrush current
Efficiency, typ.
Power factor, typ.
Internal fuse
External fuse max.
Safety class
Output voltage, adjustable 24 - 28 VDC
Static regulation accuracy
Dynamic regulation accuracy typ.
Start-up time
Hold up time of the output
Output current, continuous 24 VDC
Output current, continuous 28 VDC
Output current (power boost)
Output current, short circuit, typ.
Output ripple
Usage as battery charger
Overloading / temperature protection
Overvoltage shutdown
Relative humidity
Max. surrounding air temperature
Storage temperature
Protection class, case, EN 60529
Dimensions W x H x D; Weight
* DC operation is not included to UL approval. Customer needs to use suitable external protection.
(3) Features
[1] Input terminal:
Conductor sizes
Solid
Stranded
Stranded with ferrule with plastic sleeve
Stranded with ferrule with plastic sleeve
10
Ferrule minimum lenght must be
Use copper conductors that are designed for a minimum operating temperature of
75°C for ambient up to 60°C.
[2] Output voltage adjust 24 - 28 VDC.
[3] Bi-colour LED, output voltage "OK" - green, Alarm - red.
[4] Parallel mode switch, turn the switch to ON state when power supplies are connected in
parallel, factory setting is OFF.
[5] Output terminal:
Conductor sizes
Solid
Stranded
14
16
Stranded with ferrule without plastic sleeve
Stranded with ferrule with plastic sleeve
Ferrule minimum lenght must be
Use copper conductors that are designed for a minimum operating temperature of
11
75°C for ambient up to 60°C.
[6] Potential free alarm contact (13/14),
max. ratings 60 V AC/DC / 80 mA (resistive) SELV.
(4) Location
The power supply is cooled by natural convection. Top and bottom clearances should be 50 mm
at minimum. Min. 6 mm side clearance is recommended, if adjacent device is generating heat.
The ambient temperature should be measured on the underside of the unit. There will be an
increase of 25°C at the top. If natural convection is restricted, forced cooling should be used.
Mounting should comply with EN 60950-1 point 4.7 and 4.6.1. Protection class of the case IP20
(EN 60529).
(5) Mounting [9]
The rail should be fixed solidly so that it cannot twist when mounting or removing the unit.
Mounting instructions [7], Removing instructions [8].
12
(6) Switching on
Factory set, ready to use, check the connection diagrams for parallel and series connection.
Check the connection diagram for DC use [15].
(7) Loading capacity
The nominal current is 10 A but due to the nature of industrial loading, the power supply has
been designed to support loads with high inrush currents without damage or shutdown. Curve
[10] shows the typical voltage / current curve. Decreasing part of the curve [10] shows the
current limitation. Curve [11] shows the typical overload / temperature limit. To ensure correct
convection cooling, the unit must always be mounted with rail horizontally. Power supply is
designed to give 240% output power (power boost) for min. 5 seconds [12].
(8) Parallel connection [13]
150%
Up to 3 units may be connected in parallel. The open circuit voltage of each unit should be set
to same value. Accuracy of setting will determine how well the units share the load current. Turn
parallel mode switch to ON state. The gauge and lenght of the cable between each power supply
and the common point should be the same.
(9) Series connection
Up to 2 units may be connected in series to give either 48 VDC or +/-24 VDC. Check the
connection diagram [14].
(10) Using circuit breakers on the power supply output:
Using circuit breakers on the power supply output side up to 28 VDC we recommend MOD-EAC
module. For higher output voltages (series connection) and standard circuit breakers, power
supply will trip, for example the following ABB circuit breaker:
(11) Standards
Electrical safety
EMC
Immunity
Emissions
Overvoltage category:
We reserve the right to change this specification.
3 x 360 - 500 VAC, 500 - 700 VDC*
3 x 324 - 572 VAC, 450 - 745 VDC*
2 x 340 - 572 VAC
50/60 Hz ±6%
0,75 A / 3 x 360 VAC - 0,55 A / 3 x 500 VAC
1,12 A / 2 x 360 VAC
< 9 A / 3 x 500 VAC after 1 ms
93,7% / 3 x 400 - 93,2% / 3 x 480 VAC
0,66 / 3 x 400 VAC and 24 VDC / 10 A
0->100%, 5% 1ms / 100%->5%, 5% 1ms
> 25 ms / 3 x 400 VAC and 24 VDC / 10 A
10,0 A (+60°C) / 7,0 A (+70°C)
8,6 A (+60°C) / 6,0 A (+70°C)
Yes, with advanced parallel mode ON
5 - 95% , no condensing
-40°C - +60°C (derating 60°C - 70°C)
-40°C - +85°C
65 x 143 x 143 mm; 0,77 kg
- S201-C2A
- S201-Z4A
EN 60950-1, SELV
EN 61204-3, EMI: Class B, EMS: Industrial environment
EN 61000-4-2, ESD 6/8 kV
EN 61000-4-3, Rf-field 10 V/m
EN 61000-4-4, EFT/B 2/2 kV
EN 61000-4-5, Surge 2/4 kV
EN 61000-4-6, Cond. Rf 10 V
EN 61000-4-11
SEMI F47-0706
CISPR 22, RF-emissions
EN 61000-3-2, (valid with three phase use)
EN 61000-3-3
EN 60204-1 60 V / 1 s
II (EN 60950-1)
V1.0
3 x 6,3 A (T)
3 x 20 A (T)
1
24 VDC
+/-1%
< 400 ms
15 A / > 5 s
12 A
< 20 mV
ms
Yes
typ. 30 VDC
IP20
0,2 -10 mm² / 24 - 8 AWG
0,2 - 6 mm² / 24 - 10 AWG
0,2 - 6 mm² / 24 - 10 AWG
0,2 - 4 mm² / 24 - 12 AWG
8 mm
0,2 - 4 mm² / 24 - 12 AWG
0,2 - 2,5 mm² / 24 - 13 AWG
0,2 - 2,5 mm² / 24 - 13 AWG
0,2 - 1,5 mm² / 24 - 15 AWG
8 mm