Hubbell WS Serie Instrucciones De Instalación Y Funcionamiento página 2

Idiomas disponibles

Idiomas disponibles

OFF, the lights will remain OFF until the switch is pressed again.
If the front switch is pressed to turn the lighting ON in either mode,
the lights will stay ON with motion until the sensor times out with no
occupancy. An override switch is located behind the button cover on
the front of the sensors. (See control illustrations). NOTE: (Placing
the switch in the OFF position will turn the lights OFF regardless of
occupancy.)
To test the sensor and verify proper installation, a shortened time
delay can be used. Follow the instructions below:
(Each load controlled by separate timers.)
1. Remove wall plate and button cover on the front of the sensor.
Turn the TIME delay setting to minimum (fully counter-clockwise).
(See control illustrations).
2. Step out of the field of view of the sensor (the motion sensing LED
indicator will stop flashing). After 30 seconds the lights should turn
OFF.
3. Re-enter the field of view of the sensor. The LED will flash and the
lights will turn on. Verify the LED continues to flash with motion in
the desired field of view.
4. Manually set the timeout delay as described below.
Time Delay Setting (initially factory set to 10 minutes)
Adjust TIME delay controls to desired settings using a small
screwdriver.
Minimum setting (30 sec) is fully counter-clockwise, maximum
setting (20 min) is fully clockwise. Replace button cover and wall
plate.
GROUND
MALT / TIERRA
PD2733
Page 2
Wiring / Câblage / Cableado
03/16
loading

Este manual también es adecuado para:

Ws1020Ws1021Ws1024Ws1025Ws1020nWs1021n ... Mostrar todo