TRUEZONE ARD, EARD, AND ZD SERIES DAMPER ASSEMBLIES
Field Converting ARD Damper from Normally Open to Normally
Closed
NOTE: To have the lights and position indicator be
accurate, you would need to replace the
M847D-ZONE actuator with the M847D-
VENT actuator. If this is installed in an attic or
crawlspace which is not visible to the cus-
tomer, and having the lights and indicator be
reversed is not a concern to you, the M847D-
ZONE actuator can be used. The EARD damp-
ers come from the factory as spring-closed/
power-open dampers.
1. Remove the actuator.
2. Locate the two plastic grommets on the damper
and move them from one side to other.
3. Rotate the damper to closed position.
4. Replace the actuator on the opposite side of the
damper.
Typical Wiring Examples
TrueZONE DAMPERS TO HZ432 ZONE PANEL
M1
M4
M6
R
Fig. 1. 2-Wire Operation (Red LED only).
TrueZONE DAMPERS TO HZ432 ZONE PANEL
M1
M4
M6
R
Fig. 2. 3-Wire Operation (Red and Green LEDs).
NOTE: 2- and 3-wire operation are Power Close/
Spring Open. Additional wire only adds green
LED.
THERMOSTAT
C
K
R
C
R
U1
U1
M1
Fig. 3. EARD fresh air Damper with external
transformer.
33-00079EFS—07
M1 COMMON
M6 CLOSED
M35493
M1 COMMON
M4 GREEN LED
M6 CLOSED
M35494
SYSTEM
TRANSFORMER
C
24
120
VAC
VAC
R
EXTERNAL
TRANSFORMER
24
VAC
DAMPER
M6
EIM
POWER
HEAT
COOL
FAN
U1
U2
U3
A
B
C
D
S4
S4
S3
S3
Fig. 4. Wiring an EARD fresh air damper to a
THM5421R EIM controlled by either Prestige or
M35633
2
TO THERMOSTAT
CONV
A
SENSORS
RedLINK VisionPRO thermostat.
FURNACE
C
R
W
W2
Y
Y2
G
VENT
EARD
VENT
M35495