8. If there is a leak, turn off the gas and then tighten fittings until bubble do not appear at the
joints. Use gas PTFE thread seal tape for sealing, if it is needed. If you cannot stop the gas leak,
turn off the gas supply and have a qualified gas service technician perform a repair.
DO NOT attempt to use the kit until all gas leaks have been repaired.
9. Rinse off the leak test solution with clean water after performing the leak test.
Coupling
English
Figure 10
Generator
10ft NG Quick Connect
Hose Assembly
Figure 11
05
House NG Piping
NG Shut Off Valve
Pipe Nipple
Quick Connect Adapter
Customer Service: 1-844-FIRMAN1