ANALYZER R-440-TCP
This is a manual describing the analizer R-440-
TCP, You can find this manual in electronic format
on the Circutor web:
www.circutor.es
Before performing any maintenance,
repair or handling of any of the
connections of the equipment, must
disconnect the device from any power
source and also the connection of measurement.
When you suspect a malfunction of the equipment
please contact the service. The design of the
equipment allows a quick replacement in case of
failure.
If the equipment is used in a way not
specified by the manufacturer, the
protection guaranteed by the equipment
may be compromised.
9 DESCRIPTION OF THE R-440-TCP
The device is a mini PCL, with enough intelligence
that can control for him self the devices LM4I-4O- M
and CVM-MINI. Those devices are controlling by
the bus RS-485. The device has an Ethernet port,
10BaseT/100Base TX, for the communication with
the PC.
The R-440-TCP in total has 4 inputs, this inputs are
associates to 4 registers in the memory. The size of
the register is of 32 bits (4 bytes), every input can
count like a maximum FFFF FFFF in hexadecimal
or a 4.294.967.295 impulses.
The minimum size o changing time of the pulse has
tu be 50 ms and the minimum time between two
consecutive pulses in the same input is 50 ms. This
represent one maximum sample frequency of 10
Hz.
The R-440-TCP has 4 relay output, this output can
be
activated
o
deactivated
when
application demand the operation. The device has a
write function that is able to create for him self a
pulse of activation or deactivation. The pulse size is
variable y is programmed in the device. The
minimum value is 20 ms and the maximum value is
5.1 seconds (5100ms=255x20). The value FF (255
in decimal) multiply by 20 ms that is the minimum
value is the estimation of the real time.
10
COMUNICATION PROTOCOL
2.1
Protocol RS-485 port
It has a communication port RS485, for the
communications with the devices LM4IO-4O-M ans
CVM-MINI. For this communication the devices
©
uses
the
MODBUS
RTU
communication speed is 19200, 8, N, 1.
2.2
Protocol Ethernet port
It has an Ethernet port for communicate with the
PC. The format of the information is XML. With thi
protocol the master can configure the R-440-TCP
and the dates stored in the devices are send to the
PC.
R-440-TCP
11
TECHNICAS CHARACTERISTICS
Power supply
Power supply
Consumption
Frequency
Net interface
Interface
Connector
Protocols
Serial interface
Interface
Speed
Indicators (LED)
POWER
RX
TX
FULL / HALF
ACTIVITY
10M / 100M
LINK
Environmental conditions
Work temperature
Degree of protection
Humidity
Altitude
Dimensions
Dimensions
Security
Installation category
Type of insulation
12
LEGISLATION
2.1
Security
Category III – 300V a.c. / 520V a.c. EN-61010 Electric shock protection by
double insulation class II.
Isolation voltage between the envelope of the box and any terminal: 2500V
50Hz 1min
Isolation between the group of inputs / outputs and power input: 1 Gohm
Insulation between the group of entries and the Housing of the box: 1Gohm
13
INSTALATION
The equipment installation is performed on DIN rail, all connections being inside an electrical panel.
The computer must be connected to a power supply circuit protected with gl type fuses (IEC 269) or M type,
between 0.5 and 2 A. Should be provided with a Circuit breaker or equivalent device to disconnect the computer
from the mains. The equipment power circuit cable will be connected with minimum section 1.5 mm
14
WIRING
N
the
main
L
protocol.
The
INTERNET / INTRANET
16
SERVICE SUPPORT
In the event that operation or damage, contact your service technician CIRCUTOR, SA
TECHNICAL SUPPORT (SPAIN):
CIRCUTOR, S.A. – After sales service.
Vial Sant Jordi s/n
08232 Viladecavalls
Tel:
Fax:
Web:
Email:
85 .. 290 V A.C / 120 .. 410 V D.C
4.6 .. 7.5 VA
47 .. 63 Hz
Ethernet 10Base-T / 100Base-TX (auto sensing)
RJ45
NTP, ARP, ICMP, TFTP, DHCP, HTTP
RS-485
19200, 8, N, 1
Power supply and CPU activity
Blinking shows that we receive dates for the bus RS-485
Blinking shows that we transmit dates for the bus RS-485
Green shows that the Ethernet communication is full duplex. Amber shows that
the communication is half duplex.
Blinking in any colour shows that there is activity in the Ethernet port.
Green shows that the communication speed is 100M. Amber shows that the
communication speed is 10 M.
Activated in any colour shows the Ethernet port is has link with the router.
-10 ºC a +60 ºC
IP20
5% ...95% (without condensation)
2000m
35,4 x 84,68 x 73 mm
Category III
Type II
Note that with the connected equipment, the terminals can be dangerous to touch and the opening
of covers or removal of elements can provide access to dangerous parts to touch. The equipment
must not be used until it has completely finished installation
A
GND
B
LOAD 4
LOAD 3
LOAD 2
LOAD 1
902449459
(+34) 93 745 29 00
(+34) 93 745 29 14
www.circutor.es
15
DIMENTIONS
BUS
RS485
2.2
Standards
IEC 60664, VDE 0110, UL 94,
EN-61010-1, EN 55011,
EN61000-4-3, EN61000-4-11,
EN61000-6-4, EN61000-4-2,
EN61000-6-2, EN61000-6-1,
EN61000-6-3, EN61000-4-5