APS Installation
Configuration DIP Switch Settings*
(See Diagram 1, p. 46. Note: 1.1 is a closeup of the Configuration Dip Switches. 1.2 is "front",
1.3 is "rear").
Using a small tool, set the 4 Configuration DIP Switches (located on the bottom of your APS) to select
battery type and set the voltage range outside of which your APS will switch to battery power.
* Select before permanently mounting your APS.
• Select Battery Type
(DIP Switch #1)
CAUTION: The Battery Type DIP Switch setting must match the type of batteries you connect or your batteries may be degraded or
damaged over an extended period of time. See "Battery Selection," page 6 for more information.
Battery Type
Gel Cell (Sealed) Battery ................................. Front
Wet Cell (Vented) Battery ................................ Rear**
• Select High AC Voltage Point Switch To Battery
(DIP Switch #2)
Voltage
276V .................................................................. Front
257V .................................................................. Rear**
• Select Low AC Voltage Point Switch To Battery
(DIP Switches #3 & #4)
Rear
Front
200V
#4 Front & #3 Front
** Factory default settings.
APS INT 512 Conversion from 50 to 60 Hz.
For Qualified Service Personnel Only*
(See Diagram 2, p. 46. Note: 2.1 is the "adjustment resistor" located in the upper right-hand
corner of the component side of the circuit board).
To permanently convert the APS INT 512 to 60 Hz., qualified service personnel should open the APS
case, locate the resistor on the circuit board and remove it.
* Turn your APS OFF and disconnect from the wall outlet before 60 Hz conversion.
Electrical Connection
Plug APS INT 512 models into outlets providing 230V AC, 50 or 60 Hz. power.
4
All manuals and user guides at all-guides.com
Rear
Front
181V
#4 Front & #3 Rear
Switch Position
Switch Position
Rear
Front
162V
#4 Rear & #3 Front
Rear
Wet
Cell
Gel
Cell
Front
Rear
257V
276V
Front
Rear
Front
144V
#4 Rear
& #3 Rear**