– Setting mode = INSTALLER
(refer to the "Parameter setting levels" paragraph)
Par
Description
69*
Max. limit of delivery temp. setpoint
85
LPB–equipment address
87
Operation with timer
* According to the installation type
3.5.2
Verifying the correct recognizing
To make sure the regulator has correctly recognized the installation
on the basis of the input parameters, display the "Installatore" para-
meter on line 53 of the RVA46.531.
For Zone 1, installation n° 15 must appear; for Zone 2, installation n°
12 and for Zone 3, installation n° 11.
Par
Description
RVA46.531
Zone 1
53
Type of installation 15
Then, to display the correct communication of the PPS bus, display
the "installatore" parameter on line 62. It is possible to show the sta-
tus of several units. The buttons + / – allow switching.
RVA46.531
Zone 1
1
83
4
102
78
Default values
80
0
0
RVA46.531
RVA46.531
Zone 2
Zone 3
12
11
RVA46.531
RVA46.531
Zone 2
Zone 3
1
83
1
83
Setup
37
c
3
2
a) PPS–equipment address
b) Identification of peripheral device connected to the regulator.
c) Selected line.
The RVA46.531 regulator of Zone 1 communicates with the boiler
card, which corresponds to device n° 102, and with the QAA70 room
unit, which corresponds to device n° 83.
The RVA46.531 regulators of the Zones 2 and 3 communicate only
with the QAA70 room unit, also corresponding to device n° 83.
Device code
83
102
NOTE: The thermostat for excess temperature has the purpose
of stopping the production of heat in case the water tempera-
ture gets too high and damages the floor. We recommend set-
ting at 45°C.
a
Description
QAA70 room unit
Boiler card (BMU)
b