Gree GMV-80WL/A-T Manual Del Propietário página 27

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Model
GMV-120WL/C-T
GMV-140WL/C-T
GMV-160WL/C-T
GMV-120WL/C-X
GMV-140WL/C-X
GMV-160WL/C-X
Note:
① Selection of circuit breaker and power cord in the above table is based upon unit's maximum
(maximum current).
② Specification of power cord is based on the working condition where ambient temperature is 40℃ and
multi-core copper cable (working temperature is 90℃, e.g. power cable with YJV cross-linked copper,
insulated PE and PVC sheath) is lying on the surface of slot. If working condition changes, please adjust the
specification according to national standard.
③ Specification of circuit breaker is based on the working condition where ambient temperature of circuit
breaker is 40℃. If working condition changes, please adjust the specification according to national standard.
4.6.3 Engineering wiring of power supply and communication cable
(1)Please refer Fig. 27 and 28 for engineering wiring. If there is the hole for cable tie in
wiring route, please fix the wire with cable tie. Connect the power cord and
communication cable to the corresponding terminal board and grounding screw
according to the wiring diagram.
(2)Please be noted that engineering wiring cannot touch the pipe and appliance.
(3)This figure is only applicable for engineering wiring reference of power supply and
communication cable. If there are differences between the figure structure and actual
unit, please refer to the actual unit.
(4)For engineering wiring, please refer to the wiring diagram provided with the unit.
Fig. 27 Engineering Wiring View of GMV-80WL/A-T, GMV-100WL/A-T, GMV-121WL/A-T, GMV-80WL/C-T,
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Circuit breaker
capacity
Power supply
(A)
220~240V 50Hz
208~230V 60Hz
220~240V 50Hz
208~230V 60Hz
220~240V 50Hz
208~230V 60Hz
3N 380~415V
50/60Hz
3N 380~415V
50/60Hz
3N 380~415V
50/60Hz
DC Inverter Multi VRF System User Manual
Number of ground
wire * Min sectional
2
area (mm
32
1×4.0
40
1×6.0
40
1×6.0
16
1×1.5
16
1×1.5
16
1×1.5
24
Number of power cord
* Min sectional area
2
)
(mm
)
2×4.0
2×6.0
2×6.0
4×1.5
4×1.5
4×1.5
power

Capítulos

Tabla de contenido
loading

Tabla de contenido