Double ventilation and (OPTIONAL) batteries
Double ventilation:
If the control panel has double ventilation, we have two ventilation outputs.
The first ventilation output is VENT1 labeled, and second ventilation level is VENT2 labeled.
The alarm level in this control panels is 200 ppm.
Factory settings are as follows:
Parameter
Ventilation 1 Level:
Ventilation 1 Delay:
Post-ventilation 1 delay:
Ventilation 2 Level:
Ventilation 2 Delay:
Post-ventilation 2 delay:
Alarm Level:
Alarm Delay:
Batteries:
Batteries must be wired to the to the battery output on the board on the right side of the panel,
this output is labelled.
Value
Margins
50 ppm
Fixed
4 min
Programmable
(1 9 min)
4 min
Fixed
Fixed
100 ppm
Fixed
0 min
0 min
Fixed
200 ppm
Fixed
0 min
Fixed
Two 12V-batteries series-connected
-
+
12V
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
CCO110 / CCO115
ENGLISH
[CO]
Alarm
level
Ventilation 2
level
Ventilation 1
level
+
-
-
12V
Post-ventilation 2
Delay
Ventilation 2
Ventilation 2
OFF
Delay
Post-ventilation 1
Delay
Ventilation 2
Ventilation 1
ON
Ventilation 1
OFF
Delay
Ventilation 1
Ventilation 1
ON
ON
Alarm
Alarm
Delay
OFF
Alarm
ON
Ventilation 2
ON
Tiempo
- 17 -