Control range / Regelbereich / Gamme de réglage /
Rango de ajuste / Faixa de controlo
DC THERMOSTAT (°C)
0 - 60°C, 24 V DC
DC THERMOSTAT (°F)
32 - 140°F, 24 V DC
DC HYGROSTAT (%r.H.)
30 - 90 %, 24 V DC
External sensor + cable for
TEMPERATURE SENSOR
thermostat
External sensor + cable for
HUMIDITY SENSOR
hygrostat
3
Safety Information
These components must be installed / serviced
by
qualified
personnel
complying
relevant safety regulations in force and in
accordance
with
the
wiring
diagram
on the housing / represented in this manual.
Ensure manuals are kept in a secure place
accessible to servicing / installing personnel.
Device description
These devices have been designed specifically for
electrical enclosure temperature/humidity control.
Type
Knob colour
White
Electronic adjustable thermostat
Orange
Electronic adjustable hygrostat
Installation
The
devices
have
been
designed
installation on a DIN EN 60715 compliant rail.
For correct operation note the following:
● Device must be mounted VERTICALLY (do not
mount in any other position)
● Device must be mounted with a minimum of
30mm clearance around it to avoid covering of the
ventilation slots.
● Device must be mounted as far as possible from
heat generating components
Switching capacity
16 A, resistive load
Hysteresis
3K / 5%
Switching tolerance
±5K / 10%
Rate of temperature
max. 1K/min.
change
Operating temperatures:
-25ºC - 70ºC
Thermostats / Hygrostats
-13ºF - 158ºF
-45ºC - 120ºC
Temperature sensor
-49ºF - 248ºF
-40ºC - 85ºC
Humidity sensor
-40ºF - 185ºF 100%r.H.
Connection: 0.5 - 2.5 mm² / 14 - 20 AWG screw
terminal, Housing Material: Plastic UL94V-2
NOTE: To prevent damage to the contacts caused
by rapid switching, the device has a minimum ON
time and minimum OFF time of 2 to 3 minutes.
TO FIT SENSOR: 1. Remove blanking cover using
a screwdriver. 2. Insert centering ring with notch
positioned as shown. 3. Plug in sensor jack (sensor
housing colour must be of same colour as the
knob).
EN