General Description
ATTENTION: The SensoIRIS MC-Z addressable module
must be connected only to fire panels supporting TTE
communication protocol!
SensoIRIS MC-Z
SensoIRIS MC-Z is an addressable module designed for
Intelligent analogue addressable
application in addressable fire alarm systems, supporting TTE
conventional zone module
communication protocol. The module monitors the state of the
with built-in isolator module
connected conventional fire line and reports for its status to the
control panel.
Up to 32 conventional fire detectors can be connected to a
11
single zone.
1293
The SensoIRIS MC-Z module can detect the following states in
DoP No: 077
a conventional zone: fire, short circuit in the line, removed
Tested by EVPU: N.B.1293
detector from its base and line break (when working with
1293-CPD-0259
SensoMAG detectors series use EOL connected in parallel at
Teletek Electronics JSC
end of the line).
Address: 14A Srebarna Str,
SensoIRIS MC-Z is powered either directly from the fire panel
1407 Sofia, Bulgaria
or from external power supply unit and can be controlled via
EN54-18: 2005/AC: 2007
the communication protocol.
The module is mounted is a separate small plastic box suitable
!
Dimensions / Dimensiones /
for wall mounting, with transparent cover for visual inspection.
Размери
Installation
Attention: Power off the loop circuit before installing the
SensoIRIS MC-Z addressable module!
1. Choose the proper place for installation of the module.
2. Set the module address using SensoIRIS Programmer or
directly from addressable fire panel. The address must be in
the range from 1 to 250.
3. Run the wires to the module terminals.
4. Connect the wires to the terminals of the module according
142mm
the shown Example connection diagram.
5. Close the cover of the plastic box.
Installation / Instalación /
!
6. Test the module for proper operation and LED indication.
Инсталиране
LED Description
In normal operation mode the red LED blinks at every
IP40
communication between the module and the fire panel.
In FIRE ALARM situation the red LED light on permanently.
Indoor use
Montaje interno
The LED activation can be disabled from panel menu:
Вътрешен монтаж
-10°C ÷ +60°C
System-Programming-Devices-Loop Devices-MORE.
~230g
Outdoor use
Montaje externo
Външен монтаж
TECHNICAL SPECIFICATIONS / CARACTERÍSTICAS TÉCNICAS / ТЕХНИЧЕСКИ ХАРАКТЕРИСТИКИ
Operating voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Voltaje de funcionamiento . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Работно напрежение . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 ÷ 32 VDC
Permissible voltage ripple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pulsaciones admisibles de la alimentación . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Допустими пулсации на захранването. . . . . . . . . . . . . . . . . . . . . . . . . 3.0Vpp@27VDC
External power supply of the zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alimentación externa de la zona . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Външно захранване на зоната . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 ÷ 32 VDC
Max. current consumption with external power supply of the zone . . . . . . . . . . . . . . . Consumo máximo en alimentación externa de la zona . . . . . . . . . . . . . . . . . . . . . . Макс. консумация при външно захранване на зоната . . . . . . . . . . . . 150μА@27VDC
Max. current consumption with loop power supply (STAND-BY mode) . . . . . . . . . . . Consumo máximo en alimentación del lazo (modo DE ESPERA) . . . . . . . . . . . . . . Макс. консумация при захранване от кръга (режим ГОТОВНОСТ) . . 5.5mA
Current consumption with 1 LED ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Consumo con 1 LED conectado . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Консумация с 1 включен светодиод . . . . . . . . . . . . . . . . . . . . . . . . . . . 3mA
Max. current consumption of the detectors in ALARM mode (internal limitation):
- when the zone is powered from "+L" terminal of the loop . . . . . . . . . . . . . . . .
- when the zone is powered from "+H" terminal of the loop. . . . . . . . . . . . . . . .
Max. cross-section of the cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sección máxima del cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Макс. сечение на кабела. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5mm
Max. number of conventional detectors in one zone . . . . . . . . . . . . . . . . . . . . . . . . . . Número máximo de detectores convencionales en cada zona . . . . . . . . . . . . . . . . Макс. Брой конвенционални детектoри в зона . . . . . . . . . . . . . . . . . . 32
Relative humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Humedad relativa . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Относителна влажност . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤93% @ +40°C
Material (plastic) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Material (plástico) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Материал (пластмаса) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ABS
Color . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Color . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Цвят . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Grey/ Gris/ Сив
Installation Instructions
English
Consumo máximo de los detectores en estado de INCENDIO (límite interno):
- cuando la zona se alimenta por el borne "+L" del lazo) . . . . . . . . . . . . . . . . .
- cuando la zona se alimenta por el borne"+H" del lazo). . . . . . . . . . . . . . . . . .
Instrucciones de instalación
Español
Descripción general
ATENCIÓN: ¡SensoIRIS MC-Z podrá conectarse
únicamente a paneles que mantienen el protocolo de
comunicación TTE!
SensoIRIS MC-Z es un módulo analógico que podrá utilizarse
en sistemas de alarma de incendio analógicos que mantienen
el protocolo de comunicación TTE.
El módulo supervisa hacia el panel el estado de la zona
convencional a la que se han conectado hasta 32
detectores.
El módulo SensoIRIS MC-Z podrá detectar el acontecimiento
de los eventos siguientes en la zona convencional: incendio,
cortocircuito, detector retirado de la base e interrupción en la
línea (al trabajar con detectores de la serie SensoMAG, al final
de la línea se conectará EOL).
SensoIRIS MC-Z podrá alimentarse directamente desde el
panel o de una alimentación externa y podrá controlarse a
través de un protocolo de comunicación.
El módulo está ubicado en una caja de plástico independiente
que es apropiada para montarse en pared, con una tapa
transparente de inspección visual.
Montaje
Atención: ¡Desconecte el voltaje del lazo antes de instalar
el módulo SensoIRIS MC-Z!
1. Instalar la base de la caja en un lugar apropiado.
2. Establecer la dirección del módulo a través de SensoIRIS
Programmer o del panel. La dirección deberá estar en el
intervalo de 1 a 250, incluidos, siendo una sola la dirección
para todo el módulo.
3. Tender los cables de conexión hacia los bornes del módulo.
4. Conectar los cables del lazo, la alimentación de la zona y la
propia zona según el esquema de conexión.
5. Cerrar la tapa de la caja.
6. Ensayar si el módulo y la indicación luminosa funcionan
correctamente.
Indicación LED: descripción
En estado de funcionamiento normal, el LED rojo parpadea
durante la comunicación entre el módulo y el panel de
incendio.
En ALARMA INCENDIO, el LED rojo parpadea
constantemente. La activación de la indicación LED podrá
desconectarse desde el panel en el menú:
Sistema-Programación-Dispositivos-Lazos-OTRO.
Макс. конс. на детекторите в режим ПОЖАР (вътрешно огр.):
- когато зоната се захранва от клема "+L" на контура). . . . . . 20mA
- когато зоната се захранва от клема "+H" на контура) . . . . . 50mA
Български
Инструкции за инсталиране
Общо описание
ВНИМАНИЕ: Адресируем модул SensoIRIS MC-Z може
да бъде свързван само към панели, които поддържат
комуникационен протокол TTE!
SensoIRIS MC-Z представлява адресируем модул за
използване в адресируеми пожароизвестителни
алармени системи, поддържащи комуникационен
протокол TTE.
Модулът следи и предава на панела състоянието на
конвенционална зона, в която има свързани до 32
детектора.
Модул SensoIRIS MC-Z може да детектира настъпване на
следните събития в конвенционалната зона: пожар, късо
съединение, премахнат детектор от основата и
прекъсване в линията (при работа с детектори от серия
SensoMAG се свързва EOL в края на линията).
SensoIRIS MC-Z може да се захранва директно от панела
или от външно захранване и може да бъде контролиран
чрез комуникационния протокол.
Модулът е разположен в самостоятелна пластмасова
кутия, подходяща за стенен монтаж, с прозрачен капак за
визуална инспекция.
Монтаж
Внимание: Изключете напрежението на контура преди
да инсталирате модул SensoIRIS MC-Z!
1. Монтирайте основата на кутията на подходящо място.
2. Установете адреса на модула посредством SensoIRIS
Programmer или от панела. Адресът трябва да бъде в
интервал от 1 до 250 включително, като адресът е един за
целия модул.
3. Прокарайте кабелите за свързване към клемите на
модула.
4. Свържете кабелите на контура, захранването на зоната
и самата зона съгласно схемата на свързване.
5. Затворете капака на кутията.
6. Тествайте модула за правилна работа и светлинна
индикация.
LED Индикация - описание
В нормален работен режим червеният LED мига при
комуникация между модула и пожарния панел.
При АЛАРМА ПОЖАР червиният LED свети постоянно.
Активирането на светодиодната индикация може да се
изключи от панела в менюто:
Система-Програмиране-Устройства-Кръгови-ДРУГО.
2