CP10.122 Instruction Manual
EN
Product Description
The CP10.122 is a DIN-rail mountable single-phase-input power supply of the DIMENSION series. It
provides a floating, stabilized and galvanically separated SELV/PELV output voltage.
Intended Use
This device is designed for installation in an enclosure and is intended for general use such as in
industrial control, office, communication, and instrumentation equipment. Do not use this device in
equipment, where malfunction may cause severe personal injury or threaten human life.
Installation Notes
- This device does not contain serviceable parts. The tripping of an internal fuse is caused by an
internal defect. If damage or malfunction should occur during installation or operation, immediately
turn power off and send the device to the factory for inspection.
- Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
- Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of
the device. For other orientations see de-rating requirements in the datasheet.
- Make sure that the wiring is correct by following all local and national codes. Use appropriate
copper cables that are designed for a minimum operating temperature of 60°C for ambient
temperatures up to +45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient
temperatures up to +70°C. Ensure that all strands of a stranded wire enter the terminal connection.
- Unused screw terminals should be securely tightened.
- For use in a controlled environment. Do not use the device in pollution degree 3 areas without
additional protection or in applications where a degree of protection better than IP20 is required.
- The device is suitable to be supplied from TN-, TT- and IT mains networks. The voltage between
the L or N terminal and the PE terminal must not exceed 300Vac continuously acc. to IEC 62477-1.
- The device is designed for overvoltage category III acc. to IEC 62477-1 and II acc. to IEC 60950-1.
- The input can also be powered from batteries or similar DC sources. The voltage between the (+)
or (-) terminal and the PE terminal must not exceed 375Vdc continuously acc. to IEC 62477-1.
- A disconnecting means shall be provided for the input or output of the device when used in
applications according to CSA C22.2 No 107.1-01 or CSA C22.2 No 107.1-16.
- The device is designed as "Class of Protection I" equipment according to IEC 61140. A PE
(Protective Earth) connection is required.
- The output is electronically protected against no-load, overload and short circuit and can supply any
kind of loads, including unlimited inductive loads and capacitive loads up to 5F.
- Do not apply return voltages from the load to the output higher than 25V.
- The device is designed for convection cooling and does not require an external fan. Do not obstruct
airflow and do not cover ventilation grid (e.g. cable conduits) by more than 15%!
- The device is designed for altitudes up to 6000m. See details in the product datasheet for additional
requirements above 2000m.
- Keep the following minimum installation clearances when the device is permanently loaded with
more than 50% of the nominal current: 40mm on top, 20mm on the bottom, 5mm left and right side.
Increase the 5mm to 15mm in case the adjacent device is a heat source.
- The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL)
without additional protection device. If an external fuse is utilized, do not use circuit breakers
smaller than 6A B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker.
- The maximum surrounding air temperature is +70°C / +158°F. The operational temperature is the
same as the ambient or surrounding air temperature and is defined as the air temperature 2cm
below the device.
- For suitable accessories, such as mounting brackets or supplementary devices, see product datasheet.
Functional Description
- The output voltage can be adjusted with a small flat-blade screwdriver behind the flap on the front.
- The green DC-OK LED reports an output voltage above 90% of the adjusted output voltage of a running
device.
- The DC-OK relay monitors the output voltage and the contact is closed, when the DC-OK LED is on.
Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads.
- The device is equipped with an over-temperature protection. In case of a high temperature, the
output shut-down and starts automatically again after cooling off.
- The device is equipped with the Hiccup
output voltage falls below 6.5V), the device delivers continuous output current for 2s. After this, the
output is switched off for approx. 18s before a new start attempt is automatically performed. This
cycle is repeated as long as the overload exists. When cleared, the device will operate normally.
- Devices can be paralleled to increase the output power. The output voltage shall be adjusted to the
same value (±100mV) with the same load conditions on all devices, or the devices can be left with
the factory settings. The ambient temperature is not allowed to exceed +40°C. If more than three
devices are connected in parallel, a diode, fuse or circuit breaker with a rating of 25A or 32A is
required on each output.
- Devices of the same type can be connected in series for higher output voltages. It is possible to
connect as many devices in series as needed, providing the sum of the output voltage does not
exceed 150Vdc. Avoid return voltages from the load to the output.
- In case of an internal defect, a redundant circuit limits the maximum output voltage to 19V. The
output shuts down and automatically attempts to restart.
- The device is equipped with a remote ON/OFF function. Link pin 15 and 16 to turn the output of the
power supply off.
Headquarters: PULS GmbH, Elektrastr. 6, 81925 Munich, Germany, www.pulspower.com
Germany +49 89 9278 0
China
+86 512 62881820
PLUS
overload characteristic. At heavy overloads (when
France
+33 478 668 941
North America
+1 630 587 9780
The information in this document is believed to be accurate and reliable and may change without notice
Technical data
All parameters are typical values specified at 230Vac input voltage, 12V
16A output, 25°C ambient temperature and after a 5 minutes run-in time
unless otherwise noted.
Output voltage
Adjustment range
Output current
Input voltage AC
Mains frequency
Input current AC
Power factor
Input voltage DC
Input current DC
Input inrush current
Efficiency
Power losses
Hold-up time
Temperature range
Maximum wire size
Wire size AWG
Maximum wire diameter
Wire stripping length
Tightening torque
Maximal wire size
Wire size AWG
Maximal wire diameter
Wire stripping length
Size (wxhxd)
Weight
1) Solid / stranded wire 2) Including ferrules
Functional diagram
L
Input Fuse
Input Filter
N
Input Rectifier
Inrush Current
Limiter
Temper-
Output characteristic
Output voltage
15V
12V
6V
A: continuous current
B: intermitted current
0V
0A
Temperature range
Allowed output current at 12V
19.2A
16A
12A
A: continuous
B: short term (max. 60s)
0A
-25
Austria
+43 2764 3213
Singapore
+65 6684 2310
DC 12V
Nominal
12 – 15Vdc
Factory setting 12.0V
19.2 – 15.4A
Below +45°C ambient
16.0 – 12.8A
At +60°C ambient
12.0 – 9.6A
At +70°C ambient
Derate linearely between +45°C and +70°C
AC 100 - 240V
-15% / +10%
50 – 60Hz
±6%
1.74 / 0.92A
At 120 / 230Vac
0.99 / 0.96
At 120 / 230Vac
DC 110 - 300V
±20%
1.9 / 0.68A
At 110 / 300Vdc
6 / 9A pk
At 40°C, 120 / 230Vac
92.8 / 94.3%
At 120 / 230Vac
14.9 / 11.6W
At 120 / 230Vac
50ms
-25 to +70°C
1)
6mm² / 4mm²
Power terminals
AWG 20-10
Power terminals
2)
2.8mm
Power terminals
7mm / 0.28inch
Power terminals
1Nm / 9lb.inch
Power terminals
1)
1.5mm² / 1.5mm²
DC-OK terminals
AWG 24-16
DC-OK terminals
2)
1.6 mm
DC-OK terminals
7mm / 0.28inch
DC-OK terminals
39x124x117mm
Without DIN-rail
600g / 1.3lb
Voltage
Regulator
Power
Output
PFC
Filter
Converter
Converter
Output
Output
ature
Over-
DC-ok
Power
Shut-
Voltage
Relay
Manager
down
Protection
Remote
ON / OFF
Adjustment range
Hiccup
PLUS
mode
5A
10A
15A
20A
Output current
0
+25
+45
+60
Ambient temperature
Switzerland
+41 56 450 18 10
United Kingdom +44 1525 841001
V
OUT
+
+
-
-
-
DC-OK
LED
13
DC-OK
14
Contact
15
ON/
16
OFF
25A
+70°C