Installation instructions

EN Surge Protective Device

Item no.
Type
5093 505
V50-0-150
5093 440
V50-1-150
5093 442
V50-3-150
5093 452
V50-1+NPE-150
5093 454
V50-3+NPE-150
5093 446
V50-1+FS-150
5093 448
V50-3+FS-150
5093 460 V50-1+NPE+FS-150 Single-pole with NPE/FS L – N, N – PE 80 kA
5093 462 V50-3+NPE+FS-150 Three-pole with NPE/FS L – N, N – PE 80 kA
5095 609
C50-0-255
*
Figure
1

Product description

Lightning current and surge protection device for
equipotential bonding of power supply systems
according to VDE 0100-443 (IEC 60364-4-44)
and for lightning protection equipotential bonding
according to VDE 0185-305 (IEC 62305). For
mounting on hat rails and use in distributor hous-
ings. Arresters (Figure
individually and are encoded on the rear side, in
order to avoid incorrect connection. They pos-
sess a thermodynamic cut-off unit and have an
arresting capacity of up to 50 kA (8/20) and
12.5 kA (10/350) per pole.
If there is an error, the visual display switches
from grey to red (Figure
With snap-on hat rail bracket (Figure
The spark gap C50-0-255 is intended as an ar-
rester between the neutral conductor N and the
protective conductor (PE conductor).
Only V50-..+FS..: With module for remote sig-
nalling through potential-free changeover contact
(Figure
).

Target group

The device may only be mounted and connected
by an electrical technician.
OBO Bettermann GmbH & Co. KG
Product
Single arrester*
Single pole
Three-pole
Single-pole with NPE
Three-pole with NPE
Single-pole with FS
Three-pole with FS
Single arrester*
) can be connected
1
).
).
2
Protection
I
path
Total 8/20
L – PE/N
120
L – PE/N
37,5 kA < 350 μA
kA
L – N, N – PE 80 kA
L – N, N – PE 80 kA
L – PE/N
120
L – PE/N
37,5 kA < 350 μA
kA

General safety information

• Before working on power cables, ensure that
they are de-energised and secure them against
unintentional switch-on!
• Do not carry out mounting work during a storm!
• Comply with national laws and standards, e.g.
VDE 0100-534 (IEC 60364-5-53)!

Mounting and installation

The device can be installed in any position (e.g.
vertical or horizontal).
Figure
: VDE 0100-534 (IEC 60364-5-53)
specifies that,
– in the case of single-branch wiring,
connection length a + b
– or, in the case of V wiring,
length c
should never exceed 0.5 m.
For V wiring, use the connection terminal, item
no. 5012 010.
Caution! Risk of overloading!
The connection terminal 5012 010 is
approved for a maximum current load ≤ 50
A.
Use a suitable back-up fuse!
• Clamp the protection device onto the hat rail,
V50-...-150
Circuit
I
diagram
Total
I
PE
Figure
10/350
< 800 μA
1
3
25 kA
< 5 μA
5
50 kA
< 5 μA
7
< 800 μA
1
3
25 kA
< 5 μA
5
50 kA
< 5 μA
7