5.3.2 OnOff_status (tipo de objeto de entrada binaria)
Indica si la unidad interior está encendida o apagada.
Identificador de la
propiedad
Object_Identifier
Object_Name
Object_Type
Present_Value
Descripción
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Polarity
Inactive_Text
Active_Text
Change_Of_State_Time
Change_Of_State_Count
Time_Of_State_Count_Reset
Elapsed_Active_Time
Time_Of_Active_Time_Reset
Time_Delay
Notification_Class
Alarm_Value
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Profile_Name
© HMS Industrial Networks S.L.U. - Todos los
derechos reservados
La información contenida en este manual podrá modificarse sin
previo aviso.
Tipo de datos de la
propiedad
BACnetObjectIdentifier
CharacterString
BACnetObjectType
BACnetBinaryPV
CharacterString
CharacterString
BACnetStatusFlags
BACnetEventState
BACnetReliability
BOOLEANO
BACnetPolarity
CharacterString
CharacterString
BACnetDatetime
Unsigned
BACnetDatetime
Unsigned
BACnetDatetime
Unsigned
Unsigned
BACnetBinaryPV
BACnetEventTransitionBits
BACnetEventTransitionBits
BACnetNotifyType
BACnetArray[N] de
BACnetTimeStamp
CharacterString
Valor
(Binary Input, 0)
"OnOff_status"
BINARY_INPUT (3)
INACTIVE (0) / ACTIVE (1)
-
-
{FALSE, FALSE/TRUE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
FALSE
NORMAL (0)
"Off"
"On"
-
-
-
-
-
-
-
-
-
-
-
-
-
ASHRAE IBOX
R
R
R
R
O
O
R
R
O
R
R
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
URL https://www.intesis.com
18 / 58
R
R
R
R
-
-
R
R
R
R
R
R
R
-
-
-
-
-
-
-
-
-
-
-
-
-