5) Measures against exceeding the critical concentration
a) To control the refrigerant concentration below the critical concentration, a mechanical air
ventilating device shall be installed (for frequent air ventilating).
b) If frequent air ventilating cannot be realized, please install a leakage warning and detecting
apparatus interlinked with the mechanical air ventilating device.
b.L
(the leakage warning and detecting apparatus shall be installed in a place with dense refrigerant accumulation)
6.Trial running
critical concentration: 0.3[kg/m³]
Outdoor unit
Indoor unit
eak detection alarm device connect to mechanical ventilation
Indoor unit
0A
Fig. 6.3
Room of refrigerant leakage
All refrigerant leaked
Fig. 6.2
a.Ventilation port position