KTFD-01
DIGITAL FANCOIL THERMOSTAT
2. Select maximum setting temperature limitation.
This feature provides a maximum setpoint temperature for heating or cooling. It can be changed between
o
o
o
20
C to 35
C. The factory default setting is "35
C".
3. Select minimum setting temperature limitation.
This feature provides a minimum setpoint temperature for heating or cooling. It can be changed between
o
o
o
5
C to 20
C. The factory default setting is "5
C".
4. Memorize option before power loss
Using ▲ or ▼ button to select "rE" or "rd". "rE" means the thermostat will Memorize its ON or OFF sta-
tus before power loss. After power supply comes to normal again, the thermostat will remain ON or OFF
according to what it is before power loss. "rd" means no matter the thermostat is switched on or off be-
fore power loss, after the power supply comes to normal again the thermostat will keep power off. The
factory default setting is "rE".
5. Display backlight option
Select 1 the light will be on when any button of the thermostat is touched. The factory default is 1.
Select 2 the display will keep the light off continuously.
Select 3 the display will keep the light on continuously.
6. Fan stop option
Using ▲ or ▼ button to select "On" or "OFF". If you select "On", the thermostat will turn on the fan at a
speed provided by the Fan Switch and will not stop the fan when there is no call for heat or cool. If you
select "OFF", the thermostat will stop the fan when there is no call for heat or cool.
7. Select energy saving setpoint for heating
o
This feature allows you to set energy saving setpoint temperature for heating. The default setting is 18
C, it
o
o
can be changed between 10
Cto 18
C.