Fm Installation Drawing 5300Q502 - PR 5331 Manual Del Usuario

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Installation Drawing 5300Q502.
Model 5331C,5331D, 5333C and
Hazardous (Classified) Location
Class I,Division1, Groups, A,B,C,D
Class II Division 1 Groups E,F,G or
Class I, Zone 0, IIC
Ambient temperature limits
T4: -40 to + 85 deg. Celcius
T6: -40 to + 60 deg. Celcius
Terminal 1 , 2
Vmax or Ui: 30 V
Imax or Ii: 120 mA
Pmax or Pi: 0.84 W
Ci: 1 nF
Li:10 uH
Terminal 3,4,5,6
Only passive, or non-energy
storing devices such as RTD's
and Thermocouples may be
connected.
Model 5335C, 5335D.
Hazardous (Classified) Location
Class I,Division1, Groups, A,B,C,D
Class II Division 1 Groups E,F,G or
Class I, Zone 0, IIC
Ambient temperature limits
T4: -40 to + 85 deg. Celcius
T6: -40 to + 60 deg. Celcius
Terminal 1 , 2
Vmax or Ui: 30 V
Imax or Ii: 120 mA
Pmax or Pi: 0.84 W
Ci: 1 nF
Li:10 uH
Terminal 3,4,5,6
Vt or Uo: 9.6 V
It or Io: 28 mA
Pt or Po: 67.2 mW
Ca or Co: 3.5 uF
La or Lo: 35 mH
5300Q502.doc
2005-12-16
1
2
6
3
5
4
SENSOR
1
2
6
3
5
4
SENSOR
Rev. AD
53 3 1 V 1 1 2 - I N
5333D
Non Hazardous Location
Associated Apparatus
or Barrier
+
with
entity Parameters:
UM < 250V
Voc or Uo < Vmax or Ui
-
Isc or Io < Imax or Ii
Po < Pi
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable
This device must not be
connected to any associated
apparatus which uses or
generates more than 250 VRMS
Non Hazardous Location
Associated Apparatus
or Barrier
+
with
entity Parameters:
UM < 250V
Voc or Uo < Vmax or Ui
-
Isc or Io < Imax or Ii
Po < Pi
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable
This device must not be
connected to any associated
apparatus which uses or
generates more than 250 VRMS
1/2
17
Tabla de contenido
loading