CSA Installation Drawing 533XQC03.

5331D, 5333D and 5335D transmitters are intrinsically safe in Zone 0 Group IIC
or Class I, Division1, Group A,B,C,D when installed according to Installation
Drawing.
1. Connections with separate power supply and receiver.
Output: Standard 4 – 20 mA loop
Separate Power
Ambient temperature limits
T4:-40 to + 85 deg. Celcius
T6:-40 to + 60 deg. Celcius
Warning:
Substitution of components may impair intrinsic safety.
The transmitters must be installed in a suitable enclosure to meet installation
codes stipulated in the Canadian Electrical Code (CEC).
533XQC03.DOC
18
Receiving
Instrument
-
-
Supply
+
CSA approved
Barrier
+
1
6
5
SENSOR
2006-01-04
5333V 1 10 - I N
+
Intrinsically safe
Barrier Parameters.
Uo(Voc)
Io(Isc)
Po
Co(Ca)>Sum(Ci+Ccable)
Lo(La)>Sum(Li+Lcable)
-
5331D or
Terminal: 1-2
5333D or
Ui(Vmax) = 30 V
5335D
Ii(Imax)
Pi
Ci
Li
5331D or
Terminal: 3,4,5,6
Only passive, or non-energy
5333D
2
storing devices such as
RTD's and Thermocouples
may be connected.
3
5335D
Terminal: 3,4,5,6
4
Uo(Voc) = 9.6 V
Io(Isc)
Po
Co(Ca)
Lo(La)
Rev. AB
Non
hazardous
Location
max. 250 V
=< 30 V
=< 120 mA
=< 0.84 W
= 120 mA
= 0.84 W
= 1 nF
= 10 uH
Hazardous
Locations /
Sécurité
Intrinséque
= 28 mA
= 67.2 mW
= 3.5 uF
= 35 mH
1/2