InstallatIon InstrUCtIons
Connecting electric dryers (cont.)
USA only
warnIng
w
• Connect the power cord to the terminal block.
Each colored wire should be connected to same
color screw. Wire color indicated on manual is
connected to the same color screw in block.
Failure to follow these instructions may result in
a short or overload.
• grounding through the neutral conductor
is prohibited for: (1) new branch-circuit
installations, (2) mobile homes, (3) recreational
vehicles, and (4) areas where local codes prohibit
grounding through the neutral conductor.
three-wire connection for electric dryers:
power cord
• A 3-wire connection is NOT permitted on new
construction after January 1, 1996.
• A UL-listed strain relief is required.
1. Remove the terminal block access cover on the
upper back of the dryer. Install a UL-listed strain relief
into the power cord through-hole; then thread a UL-
listed, 30 A, 240 V, 3-wire, #10 AWg-minimum
copper conductor power cord through the strain
relief.
UL-Listed
3-Wire Power
Cord
Terminal
Block
UL-Listed
Strain Relief
• Use a 30 A, 240 V, Ul-listed power cord with #10
AWgminimum copper conductor and closed loop or
forked terminals with upturned ends.
2. Attach the two hot leads of the power cord to the
outer terminal block screws. Attach the neutral wire to
the center terminal block screw. Connect the external
ground (if required by local codes) to the green
ground screw. TIgHTEN All SCREWS SECURElY.
Reinstall the terminal block access cover.
Hot
(Black)
Ground
Screw
White Wire
from Dryer
harness
External Ground
Wire (If required
by local codes)
Neutral
(White)
Hot
(Red)