Technical Specifications - JOVENTA DAB1.4 Serie Guia De Instalacion

Tabla de contenido

Technical Specifications

DAB1.4 / DAD1.4 / DAB1 / DAD1 / DMD1.2
Product Codes
Power Requirements
Control Type
Input Signal
Feedback Signal
Motor Input Impedance
Running Torque
Travel Time
30 Seconds at 60 Hz
(for 90° of Rotation)
36 Seconds at 50 Hz
Rotation Range
91° ±2°, CW or CCW
100,000 Full Stroke Cycles;
Cycles
2,500,000 Repositions at Rated Running Torque
Audible Noise Rating
35 dBA Nominal at 1 m
Electrical Connections
1.2 m Polyvinyl Chloride (PVC) cable with 0.75 mm
Mechanical Connections
Up to13 mm Diameter Round Damper Shafts, or 10 mm Square Damper Shafts
Enclosure
NEMA 2, IP 42
Ambient Conditions
- Operating
-20 to 60° C; 90% RH Maximum, Noncondensing
- Storage
-29 to 66° C; 90% RH Maximum, Noncondensing
Shipping Weight
0.5 Kg
Compliance
- North America
UL Listed, File E27734, CCN XAPX (United States) and XAPX7 (Canada) - Actuator Housing is Plenum Rated per CSA C22.2 No. 236/UL 1995, Heating and Cooling Equipment
- European Union
CE Mark, EMC Directive 89/336/EEC
- Australia and New Zealand
C-Tick Mark, Australia / NZ Emissions Compliant
DAB1.4C / DAD1.4C / DAB1C / DAD1C / DMD1.2C
Product Codes
Power Requirements
Control Type
Input Signal
Feedback Signal
Motor Input Impedance
Running Torque
Travel Time
30 Seconds at 60 Hz
(for 90° of Rotation)
36 Seconds at 50 Hz
Rotation Range
91° ±2°, CW or CCW
100,000 Full Stroke Cycles;
Cycles
2,500,000 Repositions at Rated Running Torque
Audible Noise Rating
35 dBA Nominal at 1 m
Electrical Connections
M3 Screw Terminals
Mechanical Connections
Up to13 mm Diameter Round Damper Shafts, or 10 mm Square Damper Shafts
Enclosure
NEMA 1, IP 40
Ambient Conditions
- Operating
-20 to 60° C; 90% RH Maximum, Noncondensing
- Storage
-29 to 66° C; 90% RH Maximum, Noncondensing
Shipping Weight
0.5 Kg
Compliance
- North America
UL Listed, File E27734, CCN XAPX (United States) and XAPX7 (Canada) - Actuator Housing is Plenum Rated per CSA C22.2 No. 236/UL 1995, Heating and Cooling Equipment
- European Union
CE Mark, EMC Directive 89/336/EEC
- Australia and New Zealand
C-Tick Mark, Australia / NZ Emissions Compliant
2
DAB1.4(C) / DAD1.4(C) / DAB1(C) / DAD1(C) / DMD1.2(C)
DAB1.4
DAD1.4
2.1 VA
Floating Control without Timeout
AC 24 V +25% / -20% at 50/60 Hz, SELV Class III
---
---
2 Nm
4 Nm
60 Seconds at 60 Hz
72 Seconds at 50 Hz
conductors and 6 mm ferrule ends
2
DAB1.4C
DAD1.4C
2.1 VA
Floating Control without Timeout
AC 24 V +25% / -20% at 50/60 Hz, SELV Class III
---
---
2 Nm
4 Nm
60 Seconds at 60 Hz
72 Seconds at 50 Hz
DAB1
AC 24 V +25% / -20% at 50/60 Hz
2.5 VA
Safety Extra-Low Voltage (SELV) Class III
ON/OFF and Floating Control With Timeout
with Timeout
---
200 ohms Nominal
2 Nm
30 Seconds at 60 Hz
36 Seconds at 50 Hz
DAB1C
AC 24 V +25% / -20% at 50/60 Hz
2.5 VA
Safety Extra-Low Voltage (SELV) Class III
ON/OFF and Floating Control With Timeout
with Timeout
---
200 ohms Nominal
2 Nm
30 Seconds at 60 Hz
36 Seconds at 50 Hz
DAD1
DMD1.2
3.0 VA
3.6 VA
Modulating
DC 0(2) to 10 V or 0(4) to 20 mA
with field furnished 500 ohm resistor
DC 0(2)...10 V Corresponds to input
span selection (DC 10V at 1 mA)
4 Nm
60 Seconds at 60 Hz
60 Seconds at 60 Hz
72 Seconds at 50 Hz
72 Seconds at 50 Hz
DAD1C
DMD1.2C
3.0 VA
3.6 VA
Modulating
DC 0(2) to 10 V or 0(4) to 20 mA
with field furnished 500 ohm resistor
4 Nm
60 Seconds at 60 Hz
60 Seconds at 60 Hz
72 Seconds at 50 Hz
72 Seconds at 50 Hz
4 Nm
---
4 Nm
Tabla de contenido
loading

Tabla de contenido