INSTALLATION AND MAINTENANCE INSTRUCTIONS
MI-CR6
Six Relay Control Module
SPECIFICATIONS
Normal Operating Voltage:
Stand-By Current:
Alarm Current:
Temperature Range:
Humidity:
Dimensions:
Maximum IDC Wiring Resistance:
Accessories:
Wire Gauge:
Relay Current:
CURRENT RATING
3A
2A
1A
.5
BEFORE INSTALLING
This information is included as a quick reference installa-
tion guide. If the modules will be installed in an existing
operational system, inform the operator and local authority
that the system will be temporarily out of service. Discon-
nect the power to the control panel before installing the
modules. This system contains static sensitive components.
Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed
from the body. The housing cabinet should be metallic and
suitably grounded.
NOTICE: This manual should be left with the owner/user
of this equipment.
GENERAL DESCRIPTION
The MI-CR6 Six Relay Control Module is intended for use
in an intelligent alarm system. Each module is intended for
Form-C switching applications, which do not require wir-
ing supervision for the load circuit. A single isolated set
of dry relay contacts is provided for each module, which
is capable of being wired for either normally open or nor-
mally closed for each operation. Each module has its own
address. A pair of rotary code switches is used to set the
address of the first module from 01 to 94. The remaining
modules are automatically assigned to the next five higher
addresses. Provisions are included for disabling a maxi-
mum of three unused modules to release the addresses to
M450-03-00
15-32 VDC
1.45 mA
32 mA (assumes all six relays have been switched once and all six LEDs solid on)
-10°C to 55°C
10 to 93% Non-condensing
17.3cm H x 14.7cm W x 3.2cm D
40 ohms
Suitably grounded metallic cabinet
0.9mm2 - 3.25mm2
30 mA/Relay Pulse (15.6 mS pulse duration) pulse under panel control
MAXIMUM VOLTAGE
30VDC
30VDC
30VDC
30VDC
LOAD DESCRIPTION
Resistive
Resistive
Inductive (L/R=2ms)
Inductive (L/R = 5ms)
be used elsewhere. Each MI-CR6 module also has panel
controlled green LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
Contents include:
(6) 1 × 3 Terminal Blocks
(5) 1 × 4 Terminal Blocks
(2) 3.2 cm Stand offs
(NOTE: For the disable position, not more than one shunt shall be
installed at the same time)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected
to a compatible control panel only. The MI-CR6 Module
shall be mounted in a suitably grounded Metallic Cabinet
for EMC compliance.
1
by Honeywell
Morley IAS Fire Systems
Charles Avenue
Burgess Hill, West Sussex, RH15 9UF
APPLICATION
Non-Coded
Coded
Coded
Coded
(1) Shunts
(4) Screws
(2) Nuts
C0908-00
I56-2955-000
loading

Resumen de contenidos para Honeywell MORLEY-IAS MI-CR6

  • Página 5: Módulo De Control Con Seis Circuitos De Salida En Forma Relé

    INSTRUCCIONES DE INSTALACIÓN Y MANTENIMIENTO MI-CR6 by Honeywell Módulo de control con seis circuitos de Morley IAS Fire Systems C/Ávila 25 salida en forma relé San Sebastián de los Reyes, 28700 Madrid, Espana ESPECIFICACIONES Tensión de Funcionamiento Normal: 15-32 VDC Corriente en resposo: 1,45 mA Corriente en Alarma: 32 mA (asumiendo que los seis relés han sido conectados una vez y los seis LEDs están iluminados de forma fija) Rango de temperatura: de -10°C a 55°C; Humedad: 10 a 93% No condensada Dimensiones (mm): 185 (alto) x 147 (ancho) x 25 (fondo) Máxima Resistencia IDC del cable: 40 ohmios Accesorios: Cabina metálica conectada adecuadamente a tierra Sección del Cable:...
  • Página 6 CABLEADO NOTA: Todos los cables deben ajustarse a los códigos, orde- ura la dirección base con el número 28, a los otro cinco módulos se les adjudicarán las direcciones 29, 30, 31, nanzas y regulaciones locales. 32 y 33. NO debe configurar la dirección más baja por 1. I nstalar el cable del módulo según los dibujos y dia- encima del número 94, ya que al resto de los módulos gramas correspondientes. se les adjudicarían direcciones que no existen. 2. E fectúe las conexiones eléctricas pelando aproximada- 4. S e proporciona un puente para anular un máximo de mente unos 5 mm del aislante del cable, a continuación, tres módulos no utilizados. Estos módulos se anulan coloque el cable pelado debajo del tornillo y enrosque empezando por la dirección más alta. Si se anulan dos el tornillo.