1- Move the motor to the down end limit by using the keys "DOWN" or "UP".
2- To memorize the down end limit position, press simultaneously the buttons "STOP" and "UP". The motor
will run automatically in the up direction.
3- When the motor reaches the up End limit, press the button "STOP".
4- If necessary adjust the position with the buttons "UP" or "DOWN".
5- To memorize the up end limit position, press simultaneously the buttons "STOP" and "DOWN". The motor
will run automatically in the down direction.
6- Press 2 seconds the "STOP" button to confirm the adjustment. The motor will stop, and will run for 0,5
second in one direction, then in the other direction. Go to §5.
If you do not want to use this transmitter as the individual control:
- cut the power supply (2 seconds minimum).
- repeat the operation 4.1* with a new transmitter and then go to step §5.
* In this case, the motor will run for 0,5 second in both directions, that means the limits setting is already done.
5
Programming the first individual control point
This operation can only be performed from the
transmitter that was used for operation 4.1.
- Press
the
transmitter
approximately 1 second. The motor will run for
0,5 second in one direction and then in the other.
i
Your transmitter is now programmed to control the motor in stable mode.
Programming a new (individual, group or general) control point
6
6.1- Open the memory of the receiver from the control
transmitter:
- Press the "PROG" button of the transmitter for about
3 seconds. The motor will run for 0,5 second in one
direction and then in the other.
6.2- Confirm the operation from the new transmitter
you want to program:
- Press the "PROG" button of the transmitter for 1 second.
The motor will run for 0,5 second in one direction and
then in the other.
- For group controls, repeat operations 6.1 and 6.2 for each motor in the group.
- For general controls, repeat operations 6.1 and 6.2 for each motor in the installation.
- To delete an transmitter from the memory of a motor, perform operations 6.1 with a programmed transmitter,
then perform the operation 6.2 with the transmitter to be deleted.
EN
4/6
2
"PROG"
button
for
3
4
1
1
2
1
2
5
>>
PROG 1s.
>>
PROG ≥ 3s.
>>
PROG < 1s.
6
2s