INSTALLATION INSTRUCTIONS (CONTINUED)
Check with a qualified electrician or serviceman when the grounding instructions are not completely understood, or
when in doubt as to whether the product is properly grounded. Do not modify the plug provided; if it does not fit the
outlet, have the proper outlet installed by a qualified electrician. Only connect the product to an outlet having the
same configuration as the plug. Do not use an adapter with this product.
The 120 volt, 15 amp units can be operated on a 120 volt 15 amp circuit under the following conditions:
1. No other electrical appliances or lights are connected to the same branch circuit.
2. Voltage is 120 Volts.
3. Circuit is equipped with a 15 amp circuit breaker or a 15 amp slow blow fuse type T (For Canada use Type
D).
4. The length of copper wire between the outlet and circuit breaker is not longer than 40 feet of
14 AWG or 70 feet of 12 AWG.
Outlet - 120V / 20A
Figure 2 - 120V
Voltage
Amp
Rating
120V
25 ft.
Range
240V
50 ft.
8 - 10
14
10 - 12
12
12 - 14
12
14 - 16
12
Grounded
Outlet
Outlet - 120V / 15A
Ground
Pin
50 ft.
100 ft.
100 ft.
200 ft.
10
8
10
8
8
8
8
8
Figure 3 - 240V
Cord Length in Feet
150 ft.
200 ft.
250 ft.
300 ft.
400 ft.
500 ft.
6
6
6
6
6
4
6
6
4
4
4
4
8
Grounded
Outlet
Outlet - 240V
Ground
Pin
300 ft.
400 ft.
500 ft.
600 ft.
800 ft.
500 ft.
4
4
2
4
2
2
4
2
0
2
2
0