The values or options in the screen displays shown must be entered before start-up.
TIMER VALUES
UNLOADED START
MAX TIME @ MIN CAPACITY
COMP STARTER AUX CONTACT BYPASS
OIL PRESS BYPASS @ COMP START
CRANKCASE OIL TEMP SAFETY
CHANGEOVER
HI DSCH TEMP BYPASS @ START
AUTO RESTART AFTER POWER FAIL
FILTER DIFF PRESS SAFETY
CHANGEOVER
TRUE ANTI-RECYCLE TIMER
ACCUMULATIVE ANTI-RECYCLE TIMER (1)
NUMBER OF HOT STARTS PER HOUR (1)
NOTES:
(1)
Must be field set.
VANTAGE RECIP MICROCONTROLLER
MANUAL DE OPERACIONES
TABLE 3.
SYSTEM TIMER VALUES WORKSHEET
SYSTEM VALUES
VALUE LIMITS
1/10 COUNTS
- 39 -
DEFAULT VALUES
0/60 SEC
0/1800 SEC
0/60 SEC
0/90 SEC
0/900 SEC
0/120 SEC
60/1200 SEC
0/600 SEC
0/30 MIN
0/30 MIN
3 COUNTS
15 SEC
600 SEC
10 SEC
60 SEC
300 SEC
255 SEC
300 SEC
60 SEC
20 MIN
20 MIN