En: Installation Sheet - Aritech DB702 Hoja De Instalación

Detectores de incendio convencionales
Ocultar thumbs Ver también para DB702:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 6

EN: Installation Sheet

Description
DB702 and DB702U Mounting Bases are used with the Dx700
series of conventional fire detectors.
Figures 1 and 2 show the following:
1.
Fire alarm control panel
2.
Continuity switch
3.
First detector
4.
Remote indicator device
5.
End-of-line device
6.
Last detector
The bases feature a continuity link between LINE IN (1) and
LINE OUT (2) terminals of the conventional detector circuit.
The base is supplied with the link in closed position. This lets
you connect the zone circuit using only the bases, without
generating a fault message display at the panel.
Caution:
For general guidelines on system planning, design,
installation, commisioning, use, and maintenance, refer to
standard CEN/TS 54-14 and to local regulations.
Installing a detector in the base opens the continuity link.
Removing a detector does not automatically close the link. This
means that the panel generates a fault message when a
detector is removed.
To reset the continuity link, insert a screwdriver under the link
(Figure 3), and press up until it clips back into place (Figure 4).
Some detectors in the Dx700 series are available with a built-in
relay capability that allows the detector in alarm mode to
activate external equipment. The relay contacts (NC, C, and
NO) are shown in Figure 1.
Table 1 gives the terminal descriptions for both models.
Table 1: Terminal descriptions
Terminal
Description
1
Line in (positive)
2
Line out (positive)
3
Line common (negative)
4
NC or remote LED (negative)
5
C
6
NO
Wiring
Figures 1 and 2 show the following:
All heads are polarity insensitive. Standard wiring layout for the
detector line is shown in Figure 1 (from left to right):
Standard detector wiring
Standard detector wiring with remote indicator
Standard detector wiring with relay wiring
Wiring for connecting multiple detectors to a single remote
indicator is shown in Figure 2.
2 / 16
Maintenance
Basic maintenance of the base consists of a yearly inspection
only. Do not modify the wiring.
Specifications
Number of terminals
DB702
DB702U
Earth contact
Remote indicator option
IP rating
Temperature
Operating
Storage
Relative humidity
Colour
Dimensions (Ø × H)
DB702
DB702U
Weight
DB702
DB702U
Regulatory information
Manufacturer
Thunderous Sounders Electronics Co. Ltd.,
No, 21, Kai Fe 3rd, Pao En Industrial Area,
Ren De Village, Tainan, Taiwan, R.O.C.
EU authorized manufacturing representative:
UTC Fire & Security B.V. Kelvinstraat 7, 6003 DH
Weert, The Netherlands.
Certification r
Contact information
For contact information see our Web site
www.utcfireandsecurity.com.
CS: Instalační návod
Popis
Montážní základny DB702 a DB702U se používají společně
s konvenčními požárními hlásiči řady Dx700.
Obrázky 1 a 2 znázorňují:
1.
Požární poplachová ústředna
2.
Propojovací spínač
3.
První hlásič
4.
Externí indikační zařízení
5.
Zakončovací člen
6.
Poslední hlásič
Základny jsou vybaveny obvodem zajišťujícím propojení mezi
svorkami LINE IN (1) a LINE OUT (2) obvodu konvenčního
hlásiče. Základna se dodává s propojovacím obvodem
v sepnuté poloze. Díky tomuto uspořádání lze připojovat obvod
zóny pouze pomocí montážních základen, aniž by se na
displeji ústředny zobrazovalo hlášení poruchy.
6
6
No
Yes
IP30
−10 to +50°C
−10 to +70°C
10 to 95% noncondensing
White
100 × 9 mm
150 × 15 mm
42 g
106 g
P/N 55370146 • REV 1.0 • ISS 28JUL10