Technical Specifications - RS Pro 209-6356 Hoja De Instrucciones

Módulos de arranque suavizado sin sacudidas
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 9
V8509
Table for fault finding
Fault
1.
Drive accelerates in an
uncontrolled manner
2.
Controller suspected to
be faulty (eg following
short circuit)
3.
Everything tried without
success

Technical specifications

Electrical
Rated Voltage
Rated Frequency
Rated Motor Power
Min. Motor Power
Rated current
Max starting duty* at 4 I
:
N
- side-by-side
- intermediate spacing 10mm
EN 60947-4-2:
Loss after ramp up
Overvoltage category to IEC 664-1 (1992)/
Rated insulation voltage to PE
Terminals
D style semiconductor protection fuse type gR,
recommended RS stock no.
(for prospective short-circuit current up to 50 kA)
* starting duty refers to the percentage of operating time the RS Snatch-Free Soft-Start Module is performing soft starting.
Environment
Permissable
temperatrues:
Climatic conditions:
Pollution:
Altitude:
Safety
Relevant standards
Protective class:
IP Protection:
Installation
Weight (approx.)
Dimensions
General
RS Components shall not be liable for any liability or loss of any nature (howsoever caused and whether or not due to RS Components' negligence) which may result from
the use of any information provided in RS technical literature.
4
Possible cause
● End of ramp with full voltage comes
too early
● Controller faulty
● Power semiconductors damaged.
Check the terminals do not have a
short circuit using a Ω-meter
- Utilisation category
- Form designation
Height
Width
Depth
RS stock no. 209-6356
3AC 400V +10-15%
50/60 hz ± 2%
2.2 kW
0.25kW
5.5A
13%
16%
5.5 A: AC-53b: 4-15: 100
2 (Soft starting only)
2W
III / AC 230V only for use with TT/TN supplies with earthed neutral
II / AC 400V
1.0 - 2.5mm
2
multistrand with end ferrules
20A
422-551
Operation: 0°C to +40°C
Storage:
-25°C to +55°C
Transport -25°C to +70°C
Class 3K3 to EN 60721-3-3 (5 - 85% relative humidity). The cooling air
must have little dust and be non corrosive and non flammable.
Degree 2 to IEC 664-1 (1992):
Dry non conducting dust or particles, infrequent light condensation when
switched off permissible.
max. 2000m NN above sea level, ≥ 1000m: 1,5% / 100m power derating.
EN 60947-4-2 (1996), prEN 50178 (1996)
I to IEC 536 (1976) ie basic insulation with PE connection (protective earth).
The user is responsible for the PE connection.
IP20 to EN 60529 (1991) Finger protection
400g
75mm
45mm
120mm
Technical data subject to change without notice
Cure
- Adjustment M/R too high, turn M/R ccw.
- Return controller to supplier
- Return controller to supplier
- Send circuit diagram of application and
potentiometer settings by fax to your supplier
RS stock no. 209-6362
5.5kW
1.1kW
12A
8%
10%
12A: AC-56b: 4-15: 170
2 (Soft starting only)
2W
35A
421-520
400g
75mm
45mm
120mm
Tabla de contenido
loading

Este manual también es adecuado para:

209-6362

Tabla de contenido