Fan step
1/2/3
Heat step
Electric: Half/full power
Water: On/off (1 LED)
On/off
Fan step
1/2/3
On/off

Functional test

Functional test is started using the remote
control.
Push
and
in 5 seconds
Fan and heatings steps are tested in
10-second intervals which is indicated by
lighted LEDs. When the test is completed, all
LEDs will flash for 30 seconds.
PA2200C
Control panel
Units with electric heating and water heating
Control panel
Units with no heat
Remote control - on/off, fan steps and heating steps
Temperature control
If the temperature exceeds 50 °C, the fan
runs at full speed for 2 minutes to vent out
the heat, if the temperature rises above 50
°C again during the following 5 minutes
overheating alarm is deployed. The red LEDs
flash and all the buttons are locked.
1. Disconnect the electricity with the fully
isolated switch.
2. Determine the cause of overheating and
rectify the fault.
3. Connect the unit again.
GB
~20 °C
29