Installation of an analog input module
Please observe the following basic rules when installing the
combination sensor and an analog input module:
• One analog input module max. can be connected to the device.
• Replacement of an analog input module (if defective) by one of
the same type can be effected during operation of the system
(for this purpose, disconnect the module from the power supply).
After replacement, the weather station will reset after some 25 s.
This will re-initialize all inputs and outputs of the analog input
and of the modules connected and reset them to their original
state.
• Removing or adding modules without adapting their project
configuration and subsequent downloading into the weather
station is not allowed as this will result in malfunctioning of the
system .
Commisioning
After switching on the device for the first time, the weather station
starts a module scan (status LED: „Orange / on").
As a new device comes by default without configuration, the status
LED shows then „Red / quickly blinking".
A connected analog input module shows that it is ready for operation
by setting its own status LED to „Quickly blinking".
After connection, a combination sensor is ready for operation (as
programmed in the weather station)
After downloading a project configuration into the weather station,
the status LED shows „Green / on"; the module switches its own
status LED off.