FC AP2 ( Safe opening ) :
If the device trips during closing, it is ignored. If it trips
during opening, it Stops + gate motion is reversed for 2
sec.
FC CH1 ( Safe closing ) :
If the device trips during opening and closing, it always
Stops + gate motion is reversed for 2 sec.
FC CH2 ( Safe opening and closing ) :
If the device trips during opening, it Stops + gate motion
is reversed for 2 sec. If it trips during closing, gate motion
is reversed.
Warning: Jumper if some of these inputs used as Safety
Devices are not used.
C3) PUL and PED Input Selection:
The control unit is factory supplied with PUL control input
operation for the connection of a cyclical primary control
button (NA) and a PED input for the connection of a
cyclical Pedestrian command button (NA). If you want to
select another operating mode for the PUL and PED
inputs, proceed as follows: set SEL and SET to display C3
then press SET to select the function. At the same time
DOT 1 will start to flash, press SET to change the
function, DOT 2 will remain permanently lit and the
operation will be complete.
Repeat
the
procedure
configuration.
Accordingly, the PUL input makes it possible to connect a
button (NA) for the Opening phase only, and the PED
input for connection to a button (NA) for the Closing
phase only.
C4) PRE-FLASHING
The control unit is supplied by the manufacturer with the
Pre-flashing function disabled. If you want to enable the
function, proceed as follows: set SEL and SET to display
C4 then press SET to select the function. At the same
time DOT 1 will start to flash, press SET to change the
function, DOT 2 will remain permanently lit and the
operation will be complete.
Repeat
the
procedure
configuration.
This way, the flashing beacon output is always activated 3
seconds before automation starts any type of motion.
C5) COURTESY LIGHT:
The control unit is supplied by the manufacturer with the
Courtesy Light disabled. If you want to enable the
function, proceed as follows: set SEL and SET to display
C5 then press SET to select the function. At the same
time DOT 1 will start to flash, press SET to change the
function, DOT 2 will remain permanently lit and the
operation will be complete.
Repeat
the
procedure
configuration.
This way, the Flashing beacon output will be activated for
3 minutes, each time that an opening command is given.
C6) FLASHING LIGHT FUNCTION EVEN IN DELAY:
The control unit is supplied by the manufacturer with the
flashing beacon function during the Pause Time disabled.
If you want to enable operation, proceed as follows: set
SEL and SET to display C6 then press SET to select the
function. At the same time DOT 1 will start to flash, press
SET
to
change
the
permanently lit and the operation will be complete.
Repeat
the
procedure
configuration.
C7) DECELERATION:
The control unit is supplied by the manufacturer with the
Deceleration function enabled. If you want to disable the
function, proceed as follows: set SEL and SET to display
to
restore
the
to
restore
the
to
restore
the
function,
DOT
2
will
to
restore
the
C7 then press SET to select the function. At the same
time DOT 1 will start to flash, press SET to change the
function, DOT 2 will remain permanently lit and the
operation will be complete.
Repeat
configuration.
C8) DS1 PHOTOCELL TEST:
The control unit is supplied by the manufacturer with the
DS1 Photocell Test disabled. If you want to enable the
function (in accordance with standard EN 12453), proceed
as follows: set SEL and SET to display C8 then press SET
to select the function. At the same time DOT 1 will start to
flash, press SET to change the function, DOT 2 will
remain permanently lit and the operation will be complete.
In this way, the test will be carried out on the Photocell
connected to input DS1 before automation starts any
movement. Repeat the procedure to restore the previous
configuration.
.
C9) DS2 PHOTOCELL TEST:
The control unit is supplied by the manufacturer with the
DS2 Photocell Test disabled. If you want to enable the
function (in accordance with standard EN 12453), proceed
as follows: set SEL and SET to display C8 then press SET
previous
to select the function. At the same time DOT 1 will start to
flash, press SET to change the function, DOT 2 will
remain permanently lit and the operation will be complete.
In this way, the test will be carried out on the Photocell
connected to input DS2 before automation starts any
movement. Repeat the procedure to restore the previous
configuration.
PASSWORD : " PS " Enter / Delete
After programming the control unit, it is possible to
memorise a numerical password to disable or enable
programming of the control unit, as follows: set the SEL
key to display PS then press SET to select the function.
At the same time, DOT 1 will start to flash, press SEL and
previous
scroll through Digit 1 and 2 from 00 – 99 as desired. After
selecting the number, press SET, DOT 2 will remain lit
permanently and the operation will be complete. From this
moment on, you may view the stored settings but you
cannot change them.
To remove the Password previously entered and modify
the control unit settings, set the SEL key to display PS
then press SET to select the function. At the same time,
DOT 1 will start to flash, press SEL and scroll through
Digit 1 and 2 from 00 – 99 according to the password
previously set. After selecting the number, press SET,
DOT 2 will go off permanently and the operation will be
complete.
previous
Repeat the above operation to enter a new Safety
Password.
Important: if you enter a wrong password you have to
wait 5 minutes to repeat the operation and then 1 hour.
RESET : " RC " RESET RADIO CONTROL CODES
If you only need to delete all Radio control codes present,
proceed as follows:
set SEL to display RC then press SET to select the
function. At the same time, DOT 1 will start to flash, press
remain
SET continuously for minimum 5 seconds for DIGIT 1 and
DIGIT 2
previous
complete.
Attention: This operation does not disable the rule of the first
pre-existing radio control, if it is necessary to disable it it will be
necessary to perform a Global Reset (RS Menu).
15
the
procedure
to
restore
to display " – – " and the operation will be
Rev. 1.1
the
previous
17/04/2018