Filling The Heating System - Vaillant 301 363 Manual Del Usuario

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 16
4

Filling the heating system

6
3
Fig. 4.1
Filling the system
a
Caution!
The operating pressure of 3 bar must not be
exceeded!
3500
3000
2500
2000
1500
1000
500
9
Fig. 4.2 Usable water volume as a function of the hardness
(carbonate hardness) of the filling water
X
= Carbonate hardness of the filling water in °e
Y
= Capacity in litres
Proceed as follows to fill the heating system:
Installation manual - Water softening cartridge 806089_03
1
5
2
4
11
13
15
Filling the heating system 4
• Unscrew the yellow protective caps (1) from the
threaded connectors.
a
Caution!
Water inlet to the cartridge from below!
Observe the direction of throughflow on the
cartridge!
• Fit the water meter (2), including the supplied screw
coupling (plastic), to the bottom of the
water softening cartridge.
• Trim the supply hose (3) to the desired length and
screw it to the inlet at the bottom.
• The connection (4) from the cartridge outlet to the
combined filling and emptying valve on the boiler
must be made on site. The fitting provided (plastic)
must be installed at the outlet of the water softening
cartridge.
• To fill the heating system, first open the combined fill-
ing and emptying valve on the boiler (5) and then the
draw-off valve (6).
• Closing takes place in reverse order - first close the
draw-off valve and then the combined filling and emp-
tying valve on the boiler.
The granulate loses its effectiveness after a certain op-
erating time (see diagram in Fig. 4.2 and the sticker on
the cartridge) and must be replaced.
17
19
21
X (°e)
23
25
GB
3