Master Controller & AR-DN-FL User Interface
Overview & Modes
Cycle between Modes using the left hand Mode key and to set and change parameters within the modes using the right hand Plus key.
• The normal (default) mode is the Status Mode this is where the unit displays all the current status information. The other Modes are
accessed for either display only (Show) or for setup (Set).
• If the Mode key is pressed the modes will change as follows.
• Status » Show level » Show Type » Show Address » Show faults » Status
• If the mode key is 'long pressed' (press and hold for 3 seconds) the mode will change to Set modes and for each subsequent short
press the modes will cycle though the set modes as follows.
• Set level » Set Type » Set Address » Set faults » Set level
• When in any of the Set modes (above) you can return to normal by a long press (3 seconds) of the mode key.
Mode
Master Controller
Status
Displays the following Status.
• Minibus message receive.
• Infrared enable.
• RF message receive.
• CAN message receive.
• Infrared message receive.
Displays the following faults / errors.
• Infra red receive error.
• Mini Bus error.
• RF error.
• CAN error.
Show Level
Make all slaves display output level. The Master
Controller will display the last level it used when forcing
all slaves to the same level.
Show Type
Make all slaves display output type.
Show Address
Make all slaves display address.
Show Faults
Make all slaves display faults.
Set Level
Make all slaves display output level and allow change of
all levels together.
• Make all slaves display output level and allow change of
• Plus key (short press) cycle through set points in
• Plus key (long press) Dim up and down level ramps up
• Plus key and Mode keys (long press) 'show me' level
Set Type
Make all slaves display output type. (no "all change"
option).
Set Address
Make all slaves display address and allow automatic
re-addressing.
• Plus key (long press) start automatic readdressing of
Set Faults
Make all slaves display faults and allow reset/ clear all
faults.
all levels together by pressing the plus key.
level. 0% » 50% » 100% » 0% etc on all slaves.
and down as long as the plus key is pressed on all slaves.
will ramp up and down automatically and continually
to allow addresses to be discovered.
all slaves.
AR-DN-FL
Displays the current status information.
• Minibus message receive.
Displays the following faults / errors.
• MiniBus fault.
Displays the output level.
Displays the output type.
Displays the address.
Displays the faults.
Displays the output level and allow change.
• Plus key (short press) cycle through set points in
level. 0% » 50% » 100% » 0% etc.
• Plus key (long press) Dim up and down level ramps
up and down as long as the plus key is pressed.
• Plus key and Mode keys (long press)
Automatic ID level will 'flash' (ramp up and down)
automatically and continually to allow addresses to
be discovered.
Displays the output type and allow change.
• Plus key (short press) change output type.
Display Address (no change of address advised because
it's automatic).
• Plus key will allow change of the address this may
only required when replacing a device and setting
the same address.
Displays faults and allow fault reset/clear.
• Plus key (short press) clear slave faults.