LEGRAND Wattstopper LMPS-104 Guia De Inicio Rapido

LEGRAND Wattstopper LMPS-104 Guia De Inicio Rapido

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

No: 23545– 09/16 rev. 3
Catalog Number • Numéro de Catalogue • Número de Catálogo: LMPS-104
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
This unit is pre-set for Plug n' Go™ operation,
adjustment is optional.
For full operational details, adjustment and more features
of the product, see the DLM System Installation Guide
provided with Wattstopper room controllers, and also
available at www.legrand.us/wattstopper.
Installation shall be in accordance with all applicable
regulations, local and NEC codes. Wire connections shall
be rated suitable for the wire size (lead and building wiring)
employed.
For Class 2 DLM devices and device wiring: To be
connected to a Class 2 power source only. Do not reclassify
and install as Class 1, or Power and Lighting Wiring.
Do not apply cleaning solvent directly onto unit. Apply
cleaning solvent onto a cloth, then wipe the unit to clean it..
MOUNTING THE SWITCH
WARNING: Do Not Install To Cover a Junction Box having Class 1, 3 or
Power and Lighting Circuits.
MOVABLE WALL/PARTITION EXAMPLE
Each On/Off Wall button on the LMPS-104 represents the state of the
wall (open or closed). In the two partitions example below, Wall 1 and
2 are active (closed) and Wall 3 and 4 are inactive (open). Wall 3 and 4
are unused.
Room/
Partition 1
Closed
Wall 1
Wall 2
Wall 3
Wall 4
Active (Closed)
Room/
Room 3
1
2
Partition 2
Closed
Wall 1
Wall 2
Wall 3
Wall 4
Active (Closed)
Wattstopper
Partition Switch (version 3)
Interrupteur de partition (version 3)
Interruptor de la partición (versión 3)
Quick Start Guide • Guide de démarrage rapide • Guía de inicio rápido
SPECIFICATIONS
Voltage .............................................................................. 24VDC
Current Consumption .............................................................5mA
Power Supply ................................Wattstopper Room Controllers
Connection to the DLM Local Network .................... 2 RJ-45 ports
DLM Local Network characteristics when using LMRC-11x/2xx
room controllers:
Low voltage power provided over Cat 5e cable (LMRJ);
max current 800mA. Supports up to 64 load addresses,
48 communicating devices including up to 4 LMRC-10x
series and/or LMPL-101 controllers.
Free topology up to 1,000' max.
Environment ................................................. For Indoor Use Only
Operating Temperature .................32° to 131°F (0° to 55°C)
Storage Temperature ...................23° to 176°F (-5° to 80°C)
Relative Humidity .......................5 to 95% (non condensing)
Patent Pending
BUTTONS AND INDICATORS
Each button represents a virtual wall in the DLM space
CONNECTIVITY
The illustration below shows an example of free-topology
wiring. The LMPS switch communicates to all other Digital
Lighting Management devices connected to the low voltage
DLM Local Network, regardless of their position on the DLM
Local Network.
Occupancy
Sensor
DLM Local Network
Low Voltage
LMRJ Cables
Switch
Partition Switch
®
Green wall status LEDs
Wall status buttons
Configuration button
(behind switch plate)
Red configuration LED
Line
Voltage
Line/Hot
Neutral
Black wire
White wire
LMRC
102
Room
Controller
Yellow wire
to Load B (2)
Red wire
to Load A (1)
J-Boxes
Loads
1
2
Tabla de contenido
loading

Resumen de contenidos para LEGRAND Wattstopper LMPS-104

  • Página 1 Power Supply ........Wattstopper Room Controllers provided with Wattstopper room controllers, and also Connection to the DLM Local Network ....2 RJ-45 ports available at www.legrand.us/wattstopper. DLM Local Network characteristics when using LMRC-11x/2xx room controllers: Installation shall be in accordance with all applicable Low voltage power provided over Cat 5e cable (LMRJ);...
  • Página 2: Setup And Configuration

    PLUG N’ GO (PNG): DEFAULT OPERATION Upon initial power up, the DLM system automatically identifies the devices on the Local Network and the system then uses the Plug n’ Go™ configuration appropriate to the number of loads and types of devices on the DLM Local Network. If the LMPS is never configured, the system defaults to PnG and ignores LMPS.
  • Página 3 Alimentation électrique ....Wattstopper contrôleur de pièce DLM fourni avec Wattstopper contrôleurs de pièce et aussi disponible au Connexion au réseau local DLM ........2 ports RJ-45 www.legrand.us/wattstopper. Caractéristiques du réseau local DLM pendant l'utilisation des contrôleurs de pièce LMRC-11x/2xx: L'installation doit être effectuée conformément à tous les règlements La basse tension est générée par le câble Cat 5e (LMRJ);...
  • Página 4: Boutons Et Voyants

    BOUTONS ET VOYANTS EXEMPLE DE DEUX MURS AMOVIBLES/PARTITIONS Chaque bouton marche/arrêt du LMPS-104 représente l’état du mur (ouvert ou fermé). Dans l’exemple à deux partitions ci-dessous, DEL d'état de mur vert les murs 1 et 2 sont actifs (fermés) et les murs 3 et 4 sont inactifs (ouverts).
  • Página 5 En mode PnL avec le LMPS en réseau local, tous les périphériques sont déconnectés (DEL bleues désactivées) et doivent être sélectionnés, puis raccordés aux charges appropriées. Étape 3 : Sélection de la charge Appuyez sur le bouton de configuration puis relâchez-le pour naviguer parmi les charges raccordées au réseau DLM local. Lors de l’activation de chaque charge, sélectionnez les périphériques (boutons et capteurs d’interrupteur) à...
  • Página 6: Especificaciones

    Suministro de energía ..Controladores de habitación Wattstopper proporciona con los controladores de habitación Wattstopper; también Conexión a la red local DLM ........2 puertos RJ-45 está disponible en www.legrand.us/wattstopper. Características de red local DLM al usar controladores de habitación LMRC-11x/2xx : La instalación debe realizarse conforme con todas las...
  • Página 7: Ajustes Y Configuración

    PLUG N’ GO (PNG): FUNCIONAMIENTO PREDETERMINADO Después del encendido inicial, el sistema DLM automáticamente identifica los dispositivos de la red local y luego el sistema utiliza la configuración de Plug n’ Go™ adecuada según el número de cargas y tipos de dispositivos de la red local de DLM. Si el LMPS nunca es configurado, el sistema utiliza PnG en forma predeterminada y omite al LMPS.
  • Página 8: Solución De Problemas

    No. 23545 – 09/16 rev. 3 © Copyright 2016 Legrand All Rights Reserved. © Copyright 2016 Tous droits réservés Legrand. 800.879.8585 © Copyright 2016 Legrand Todos los derechos reservados. www.legrand.us/wattstopper...

Tabla de contenido