No: 23545– 09/16 rev. 3
Catalog Number • Numéro de Catalogue • Número de Catálogo: LMPS-104
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
This unit is pre-set for Plug n' Go™ operation,
adjustment is optional.
For full operational details, adjustment and more features
of the product, see the DLM System Installation Guide
provided with Wattstopper room controllers, and also
available at www.legrand.us/wattstopper.
Installation shall be in accordance with all applicable
regulations, local and NEC codes. Wire connections shall
be rated suitable for the wire size (lead and building wiring)
employed.
For Class 2 DLM devices and device wiring: To be
connected to a Class 2 power source only. Do not reclassify
and install as Class 1, or Power and Lighting Wiring.
Do not apply cleaning solvent directly onto unit. Apply
cleaning solvent onto a cloth, then wipe the unit to clean it..
MOUNTING THE SWITCH
WARNING: Do Not Install To Cover a Junction Box having Class 1, 3 or
Power and Lighting Circuits.
MOVABLE WALL/PARTITION EXAMPLE
Each On/Off Wall button on the LMPS-104 represents the state of the
wall (open or closed). In the two partitions example below, Wall 1 and
2 are active (closed) and Wall 3 and 4 are inactive (open). Wall 3 and 4
are unused.
Room/
Partition 1
Closed
Wall 1
Wall 2
Wall 3
Wall 4
Active (Closed)
Room/
Room 3
1
2
Partition 2
Closed
Wall 1
Wall 2
Wall 3
Wall 4
Active (Closed)
Wattstopper
Partition Switch (version 3)
Interrupteur de partition (version 3)
Interruptor de la partición (versión 3)
Quick Start Guide • Guide de démarrage rapide • Guía de inicio rápido
SPECIFICATIONS
Voltage .............................................................................. 24VDC
Current Consumption .............................................................5mA
Power Supply ................................Wattstopper Room Controllers
Connection to the DLM Local Network .................... 2 RJ-45 ports
DLM Local Network characteristics when using LMRC-11x/2xx
room controllers:
Low voltage power provided over Cat 5e cable (LMRJ);
max current 800mA. Supports up to 64 load addresses,
48 communicating devices including up to 4 LMRC-10x
series and/or LMPL-101 controllers.
Free topology up to 1,000' max.
Environment ................................................. For Indoor Use Only
Operating Temperature .................32° to 131°F (0° to 55°C)
Storage Temperature ...................23° to 176°F (-5° to 80°C)
Relative Humidity .......................5 to 95% (non condensing)
Patent Pending
BUTTONS AND INDICATORS
Each button represents a virtual wall in the DLM space
CONNECTIVITY
The illustration below shows an example of free-topology
wiring. The LMPS switch communicates to all other Digital
Lighting Management devices connected to the low voltage
DLM Local Network, regardless of their position on the DLM
Local Network.
Occupancy
Sensor
DLM Local Network
Low Voltage
LMRJ Cables
Switch
Partition Switch
®
Green wall status LEDs
Wall status buttons
Configuration button
(behind switch plate)
Red configuration LED
Line
Voltage
Line/Hot
Neutral
Black wire
White wire
LMRC
102
Room
Controller
Yellow wire
to Load B (2)
Red wire
to Load A (1)
J-Boxes
Loads
1
2