9 Remote Air Temperature Sensor

NO
CN15
Notes:
① Distance between the monobloc unit and the remote air temperature senor should be less than
15 meters due to length of the connection cable of remote air temperature sensor;
② Height from floor is approximately 1.5 meters;
③ Remote air temperature sensor can not be located where the area may be hidden when door is
open;
④ Remote air temperature sensor can not be located where external thermal influence may be
applied;
⑤ Remote air temperature sensor should be installed where space heating is mainly applied;
⑥ After the remote air temperature sensor is installed, it should be set to "With" through the wired
controller so as to set the remote air temperature to the control point.