IMPORTANT: For your safety, read and understand instructions completely before starting installation. Before wiring to power supply,
turn off electricity at the fuse or circuit breaker box.
NOTE: Juno recessed products are designed to meet the latest NEC requirements and are classified in compliance with the applicable UL standards.
Before attempting installation of any recessed lighting product, check your local electrical building code. This code sets the wiring standards and installation
requirements for your locality and should be understood before starting work. Suitable for wet location in indoor covered ceiling applications only.
SAVE THESE INSTRUCTIONS
Product Information
Juno 4RLD, 5RLD and 6RLD LED trims may be used as retrofit trims for incandescent housings already installed in application or with dedicated
quick connect housings by Juno.
The retrofit trims consist of the following: Retrofit trim with quick connect, medium base socket adaptor with mating quick connect,
and installation instructions. Check for all contents prior to installation.
Do not make or alter any open holes in an enclosure of wiring or electrical components during kit installation.
WARNING - Risk of fire or electric shock.
• Do not alter, relocate, or remove wiring, lampholders, power supply, or any other electrical component.
• Installation of this retrofit assembly requires a person familiar with the construction and operation of the luminaire's electrical system
and the hazard involved. If not qualified, do not attempt installation. Contact qualified electrician.
• Install this kit only in luminaires that have the construction features and dimensions described in these instructions, and where the input
rating of the retrofit kit does not exceed the input rating of the luminaire.
AVERTISSEMENT - Risque d'incendie ou d'électrocution
• Ne modifiez pas, ne déplacez pas et n'ôtez pas le câblage, les porte-lampe, le bloc d'alimentation ou tout autre composant électrique.
• L'installation de cet assemblage modifié exige une personne familière avec la construction et le fonctionnement du circuit électrique
de l'appareil d'éclairage et les risques encourus. Si vous n'êtes pas qualifié, n'essayez pas le montage. Mettez-vous en rapport avec
un électricien qualifié.
• Ne montez ce nécessaire que sur des luminaires dotés des caractéristiques de construction et des dimensions décrites dans ce
mode d'emploi, et où la classification de débit calorifique du nécessaire d'adaptation n'excède pas la classification de débit
calorifique du luminaire.
WARNING - To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
AVERTISSEMENT - Afin d'éviter tout endommagement ou abrasion du câblage, ne mettez pas en contact le câblage avec les arêtes
de la tôle ou d'autres objets tranchants.
THIS RETROFIT KIT IS ACCEPTED AS A COMPONENT OF A LUMINAIRE WHERE THE SUITABILITY OF THE COMBINATION
SHALL BE DETERMINED BY CSA OR AUTHORITIES HAVING JURISDICTION.
Dimming
Juno retrofit LED trims require 120VAC input and are dimmable with most incandescent, magnetic or electronic low voltage wall box dimmers*.
Contact Juno Lighting Group Product Services or visit www.junolightinggroup.com for a current list of compatible dimmers.
Retrofit trim is suitable for wet locations in indoor covered ceilings only.
Trim assembly has integral LED electronics. Replace entire trim assembly in the event of failure.
*Electronic low voltage dimmers require a neutral wire connection in the wall box.
Juno Retrofit LED Trim Compatibility
Juno Retrofit LED trims are designed to work with most standard UL listed recessed
incandescent housings. When used with standard medium base incandescent housings,
the medium base socket adaptor must be used. Housing compatibility can be determined by
measuring the recessed housing diameter and height as shown in Figure 1. Refer to the chart
for compatible size ranges. Housing construction features vary. The height and diameter chart
should be used as a guideline. Actual installation is the best method of determining compatibility.
4"
Internal Diameter
4" - 4 1/2"
Internal Height
4" min.
Minimum lamp compartments:
50 in
3
(819 cm
3
) for Model 4RLD,
78 in
3
(1278 cm
3
) for Model 5RLD,
103 in
3
(1687 cm
3
) for Model 6RLD
1300 S. Wolf Road • Des Plaines, IL 60018 • Phone 800-323-5068 • Visit us at www.acuitybrands.com/juno-recessed
©2017 Acuity Brands Lighting, Inc
INSTALLATION INSTRUCTIONS
For 4RLD, 5RLD & 6RLD Retrofit Trim Series
5"
6"
5" - 5 3/4"
5 3/4" - 7"
4" min.
4" min.
Rev 2/19
P6170
Internal
Height
Internal
SEE
Diameter
CHART
Figure 1
1 of 2