Troubleshooting Guide - DeVillbiss PowerBack GM1000 Manual Del Operador

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

PROBLEM
Engine will not
start
No electrical
output
Repeated
circuit breaker
tripping
Generator
overheating
A04669

TROUBLESHOOTING GUIDE

CAUSE
1.
Low on fuel or oil.
2.
Engine On/Off switch in
Off position.
3.
Faulty spark plug.
4.
Choke in wrong position.
5.
Fuel valve lever in closed
position
6.
Unit loaded during
start-up.
7.
Spark plug wire loose.
8.
Fuel line clogged.
9.
Faulty ignition system.
1.
Faulty receptacle.
2.
Circuit breaker kicked
out.
3.
Defective capacitor.
4.
Faulty power cord.
1.
Overload
2.
Faulty cords or
equipment
1.
Generator overloaded.
2.
Insufficient ventilation.
1.
Add fuel or oil.
2.
Place in the ON position
3.
Replace spark plug.
4.
Adjust choke accordingly.
5.
Open fuel valve lever.
6. Remove load from unit.
7. Attach wire to spark plug.
8. Clean fuel line and fuel filter.
9. Consult a Service Center.
1. Have Service Center replace.
2. Depress and reset.
3. Have Service Center replace
capacitor.
4. Repair or replace cord.
1.
Reduce load.
2.
Check for damaged, bare, or
frayed wires on equipment.
Replace.
1. Reduce load.
2. Move to adequate supply of
fresh air.
22- ENG
CORRECTION
Tabla de contenido
loading

Productos relacionados para DeVillbiss PowerBack GM1000

Tabla de contenido