Tools And Material; Locating The Unit; Planning Of The Ductwork; Installing Non -Insulated Ducts And Diffusers - Broan HRVH100SE Manual De Instalación

Ocultar thumbs Ver también para HRVH100SE:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

3. I
(
'
NSTALLATION
CONT
3.2 T
M
OOLS AND
ATERIAL
Following are the tools and material needed:
Phillips no. 2 or Robertson no. 2 screwdriver
Small flat blade screwdriver (for wall control connection)
Wire stripper (for wall control connection)
Hammer and flat blade screwdriver (for plenum connection installation only, to make holes in existing metal duct)
Scissors or utility knife (to cut duct tape)
Measuring tape
Duct tape
Tin snips or metal shear (for plenum connection installation only, to cut ductwork)
Aluminum duct tape (for plenum connection installation only)
Jig saw
Caulking gun and caulking.
3.3 L
OCATING THE UNIT
Choose an appropriate location for the unit.
Within an area of the house where the ambient temperature is kept between 50°F (10°C) and 104°F (40°C).
Away from living areas (dining room, living room, bedroom), if possible.
So as to provide easy access to the interior of the unit, for maintenance.
Close to an exterior wall, so as to limit the length of the insulated flexible duct to and from the unit.
Away from hot chimneys and other fire hazards.
Allow for a power source (standard 3-prong grounding outlet).
FOR HRV UNITS ONLY: Close to a drain. If no drain is close by, use a pail to collect
run-off.
Hang the unit with the four hooks, chains and springs provided. See illustration at right.
Make sure the unit is level.
3.4 P
LANNING OF THE
Keep it simple. Plan for a minimum of bends and joints.
Keep the length of insulated ducts to a minimum.
Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the exhaust air from a dryer or a range hood. This
would cause clogging of the filters and recovery module.
If the house has two floors or more, be sure to plan for at least one exhaust register on the highest lived-in level.
3.5 I
N
-I
NSTALLING
ON
NSULATED
3.5.1 F
D
ULLY
UCTED
Never install a stale air exhaust diffuser in a closed room where a combustion device operates, such as a
gas furnace, a gas water heater or a fireplace.
Stale air exhaust ductwork
Install the stale air exhaust diffuser in the main area where the contaminants are produced: kitchen, living room, etc. Position
the diffuser as far from the stairway as possible and in such a way that the air circulates in all the lived-in spaces in the house.
If desired, you can install another diffuser (sold separately).
If a diffuser is installed in the kitchen, it must be located at least 4 feet (1.2 m) from the range.
Install the diffuser 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall OR install it in the ceiling.
)
D
CAUTION
D
UCTWORK
D
D
UCTS AND
IFFUSERS
S
(
S
YSTEM
AS ILLUSTRATED IN
2.1)
ECTION
!
WARNING
6
VD0305