The "DA.90BM" control unit with microcontroller is suitable for motors with up to 500W total power.
N.B.: If two motors are used on an overhead door, the two 9
µ
by a 16
F capacitor.
The "Adjustment of the motor torque" can be carried out using the 5-position switch.
This switch should be placed in the position in which, once the automation has started, it can be stopped
if it comes up against a certain amount of resistance. This acts as a safety function to protect people or
things from impact.
Installation instructions.
a)
The electrical installation and functioning logic must comply with current standards.
b)
Keep the power cables (for the motor and power supply) away from the control cables (buttons,
photocells, radio). To avoid interference use two separate sheaths (see EN 60204-1 15.1.3).
c)
Check all the connections again before supplying voltage.
d)
Check that the Dip-Switch settings are as required.
e)
When voltage is supplied, the "POWER" led should light up. If this is not the case, check the state
of the fuses and whether 230 VAC 50 Hz power is present between terminals 1 and 2 (INPUT 230VAC
- respect phase/neutral wire position).
f)
The N.C. inputs not used must be connected to the common "+V".
g)
If the direction of the motor rotation is not correct, invert the "OPEN" - "CLOSE" wires of the motor
as well as the wires of the "FCA" - "FCC" limit switches.
h)
If the overhead door has a pedestrian door and a microswitch connected to the Stop, check that
this microswitch is not subject to vibrations during opening or closing.
Input/Output functions
(1,2)
INPUT 230VAC= Control unit 230VAC 50 Hz power supply
(3,4,5)
COM/APRE/CHIUDE= Connection to the corresponding 230VAC 50 Hz motor terminals
(6,7)
LAMP230= Connection to the 230VAC blinker.
(10,11) LAMP24= Connection to the 24VAC blinker.
(8,9)
CORT 230= Connection to the 230VAC courtesy lamp.
(12,13) ELS= Connection to the 24VAC electric lock.
(14,15) OUT 24VAC= 24VAC auxiliary power supply output (1A max.).
(16,17) +V= Common connection to all the control inputs.
(18)
FTC= Photocell receiver input (n.c. contact).
(19)
FCA= Input of limit switch for opening slow-down start (n.c. contact).
(20)
FCC= Input of limit switch for closing slow-down start (n.c. contact).
(21)
STOP= STOP button input (n.c. contact).
(22)
P.P.= STEP-by-STEP button input (n.o. contact).
(23)
APRE= OPEN button input (n.o. contact).
6
DA.90BM Control unit with microcontroller
(respect phase/neutral wire position).
(the earth wire (green/yellow) must be connected to the motor housing).
µ
F capacitors must be removed and replaced