WARNING
!
Hazardous voltages are present in this electrical equipment during operation.
Failure to handle the equipment properly can therefore result in death, severe personal injury or substantial property damage.
Only qualified personnel should work on or near this equipment.
The product will function correctly and safely only if it is properly transported, stored, set up and installed.
The main plant switch must be switched off and secured against reconnection prior to installation or maintenance of the equipment. Failure to
disconnect the main switch means that contact with live parts could result in death or severe personal injury.
To operate the unit in 120V mode, the switch on the side panel under the cover (see picture on page 3 for location) must be set to the 120V
position.
IMPORTANT
The unit may only be opened by properly trained personnel. Contains electrostatically sensitive components!
Description and design
The SITOP 24V/5A and 24V/10A power supplies are chassis-mounted units. The devices must be installed in accordance with the relevant DIN/VDE standards
or national codes of practice. The equipment is to be provided with fixed connecting leads.
Primary switched-mode power supplies for connection to 1-phase AC systems or to 2 phases of three-phase systems (TN, TT or IT (≤3AC 500V) systems in
accordance with VDE 0100 T 300 / IEC 364-3) with rated voltages 120-230V / 230V to 500V , 50/60Hz; output voltage +24V DC, floating, short-circuit-proof and
stable at no load.

Technical data

6EP1 333-3BA00
6EP1334-3BA00
Input variables
Rated input voltage U
:
e
AC 120-230 / 230V-500V,
50/60Hz
Operating voltage range:
85-264/176-550V
Surge resistance:
1300V
/ 1,3ms
p
1)
Mains buffering at 120/230V
:
25ms
25ms
Input current I
at 120/230V:
e
2.2/1.2A
4.4/2.4A
rms
Making current limitation (25°C) standard
2
<35A, <1.7A
s
<35A, <4.0A
Recommended circuit-breaker characteristic C (or
B),
6A (10A) for 1-phase AC systems
A two-pole coupled line-protection circuit-breaker or
motor-circuit breaker using the outer contact pairs
must be provided as a protection device for two-
phase operation on 2 outer conductors of a three-
phase system,
e.g. 3RV1021-1EA10 (setting 3.8A) at 230V
e.g. 3RV1021-1DA10 (setting 3A) at 400/500V
Efficiency at full load (typical):
86%
86%
Power consumption (active power):
140W
280W
Installation instructions
Mount on standard DIN rail DIN EN 50022-35x15/7.5. To ensure proper cooling, the device must be mounted vertically such that the input and output terminals
are at the bottom. A clearance of 50 mm in each case must be left above and below the device.
The supply voltage connection (AC 120V/230V) must be made in accordance with VDE 0100 and VDE 0160. A protective device (circuit-breaker) and
interrupter must be provided for safe disconnection of the power supply. If the power pack is operated between phases L1 and L2, and an r.c.d. is used as
protection against direct or indirect contact, then the r.c.d. must be a universal device (type B).
Parallel operation and selectable short-circuit behavior
Selector switch
Function
A
For load distribution in parallel operation, the devices can be switched from single mode (switch setting OFF) to parallel mode (switch
setting ON). Switch setting ON produces an inclined output characteristic
B
In switch setting OFF (constant current mode), the device supplies a constant current of about 1.15 x rated current in the case of an
overload/short circuit. In switch setting ON (shutdown mode), the device is shut down if it is overloaded for more than about 100 ms. This
status can be reset by Power OFF for at least 5 seconds followed by Power ON.
Connection and terminal assignments
Terminals
Function
L1, L2 (N)
Input voltage AC 120V.. 500 V
PE
PE conductor
1, 2
DC 24 V output voltage
1)
Supplementary module 6EP1961-3BA00 is available for longer mains buffering periods up to max. 3 s and supplementary module 6EP1961-3BA10 for
annunciation signals (input voltage, output voltage) and remote ON/OFF circuit.
2)
supply voltage 208V, selector switch position 120V
SIEMENS AG ÖSTERREICH, 10.2007
Output variables
Output DC voltage U
Delivery state: 24V ±1%
Setting range: 24V to 28.8V, set via potentiometer
on front of unit (see page 3 for position)
Derating at U
> 24V:
a
4% I
or 3°C t
a
amb
Output voltage ripple:
<50mV
residual ripple
pp
<200mV
peaks
pp
Direct output current I
0-5A
rms
2
s
Two identical devices can be connected in parallel
to increase the power output. Switchover of output
characteristic using selector switch A (see page 3
for position).
Environment
Temperature
for storage and shipment:
for operation:
Humidity rating according to climatic category 3K3
to EN 60721, Part 3; no condensation
Natural air cooling
Pollution degree 2
Weight
1.2kg
(see page 3 for selector switch position and setting)
Terminal capacity
0.2...2.5mm
0.2...2.5mm
:
a
/ V U
a
:
a
0-10A
-25°C to +85°C
0°C to +60°C
1.4kg
Remarks
2
Screw-type terminals: Use a screwdriver with blade width of 3.5mm.
Recommended tightening torque 0.5...0.6 Nm (5-7 Lb-in)
2
Use copper wire rated 65 / 75°C
5/9
Protective and monitoring
functions
Static current limitation: Typ. 1.15 x I
Behavior under short-circuit conditions (output):
Constant current / shutdown, directly via selector
switch B (see page 3 for position)
Signaling:
LED green: Output voltage >20.5V
LED amber: Overload, output voltage < 20.5V
(in "Constant current" mode only)
LED red:
Latched shutdown
(in "Shutdown" operating mode only)
or Remote Off via supplementary
module 6EP1961-3BA10
1)
Annunciation signals
Standards
Degree of protection: IP20 to IEC 529
Protection class 1
Safety to VDE 0805 (EN 60950): SELV
Safety separation afforded according to EN60950;
EN 50178;VDE 0100 Part 410; EN61140+EN
60947-1 (equivalent to VDE 0140+VDE 0660 Part
100, replacing VDE 0100 Part 101); UL508; CSA
C22.2; SEMI F47 compliance Test
Interference emission to EN50081-1
RI suppression according to EN 55022, limit-value
curve B
Interference immunity to EN 61000-6-2
Limitation of input current harmonics to
EN 61000-3-2
SITOP modular 5A / 10A 1/2phasig