6- Technical specifications
•
Mains voltage
•
Mains fuse
•
Power
•
Working temperature
•
Humidity
•
Nº. of areas per station
GB
•
Dimensions (width-height-depth)
•
Material
•
Technology
•
Power supply
•
Measurement scale
•
Area connection
•
Loop distance
•
Nº of detectors per area
•
Extraction 1 outputs
•
Extraction 2 outputs
•
Alarm output
•
Programmable extraction 1 level
•
Programmable extraction 2 level
•
Programmable alarm level
•
Extraction operation mode
•
Maximum consumption
• Data presentation
•
Technology
•
Power supply
•
Connections
•
Quiescent drain
•
Consumption at alarm upper level
•
Useful life of the sensor
•
Measurement range
•
Sensor response time
•
Material
Specifications of the station
From 1 to 3 (Modular can be extended)
Specifications of area module
Relay contact (C,NC,NO) I max= 5 A
Relay contact (C,NC,NO) I max= 5 A
Relay contact (C,NC,NO) I max= 5 A
Programmable from 0 to 0 a 299 pmm
Programmable from 0 to 299 pmm
Automatic by maximums, automatic
3 displays 7 segments plus 8 LED indicators
Specifications of the detectors
Electrochemical cell and microprocessor
5 years (depending on the environment of use)
20
230VAC ±10%
250VAC 4A 5x20
45W
Between -5º y 40º C
Maximum 95% non-condensing
439 mm x 268 mm x 112 mm
ABS
Latest generation microprocessor
From 21 to 29 Vdc
From 0 to 300 pmm of CO
2 wires
2 Km cable 1,5 mm
32 remote sensors
(factory set 100 pmm)
Programmable from 0 to 299 ppm
(factory set 100 ppm)
(factory set 150 ppm)
by average, OFF, ON.
100 mA @ 28 Vdc
From 21 to 29 Vdc
2 non-polarised wires
< 1 mA
< 5 mA
From 0 to 300 ppm of CO
60 s
ABS
2