Hitachi CH-6.0N2 Manual De Instalación Y Funcionamiento página 22

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 25
ELECTRICAL WIRING
The following figure shows the example of electrical wiring around the CH units. Refer to the Technical Catalog for Outdoor Unit
regarding the electrical wiring of the whole system.
Outdoor Unit
Power Supply
AC 1~ 220-240V/50Hz
CB
Earth Leakage
Breaker (ELB) and
Circuit Breaker (CB)
NOTE:
- Do not apply excessive voltage to the operating line (DC5V (non-pole)) between outdoor unit and CH unit, between CH unit
and indoor unit, between CH units.
- Use 2-Core cable for the operating line. (Do not use 3-Core cable or over.)
- Connect the operating line for the outdoor unit to the terminal "1" and "2" of TB2 on the CH unit.
- Connect the operating line for the indoor unit exclusively for cooling operation to the terminal "1" and "2" of TB2 on the CH unit.
- For the CH unit in the same refrigerant cycle, electrical power source can be supplied by one switch.
- Do not connect the power supply line (220V~240V) to the terminal board for operating line.
- Connect the earth wire for the outdoor/indoor units and CH unit. The ground wiring work under the condition of 100W (max.)
ground resistance should be performed by the qualified electrician.
Ensure that DSWs on the PCB1 are set before shipping as shown below and no setting is required.
DSW1
ON
1 2
1 2 3 4 5 6
22
Outdoor Unit
Connect the operating line for
the outdoor unit to the terminal
"1" and "2" of TB2 on the CH unit.
TB2
Operating Line
(Non-pole, DC5V)
DSW101
DSW301
ON
ON
1
1
2
2
PMML0309A rev.1 - 09/2015 - P5416573
CH Unit
CH Unit
Remote
Indoor Unit
Indoor Unit
Control
Switch
In case that the multiple indoor units
are connected to the same CH unit,
the operation mode (cooling/heating)
for the indoor units will be the same.
Setting of Dip Switches
NOTE:
- The "
" mark indicates position of dip switches. Figures
show setting before shipment.
CAUTION:
- The control of the temperature is only available through the
room's thermostat or Aquastat. The Remote Control Switch
of the indoor unit cannot be touch, if it is done the unit will
be outside of warranty.
- Before setting dip switches, firstly turn OFF power source
and set the position of the dip switches. If the switches are
set without turning OFF the power source, the switches can
not function.
Connect the operating line for
the indoor unit (exclusive use of
cooling operation) to the terminal
"1" and "2" of TB2 on the CH unit.
Remote
Indoor Unit
Indoor Unit
Control
(Exclusive Use of
Switch
Cooling Operation)
Remote
Control
Switch
Tabla de contenido
loading

Este manual también es adecuado para:

Ch-10.0n2

Tabla de contenido