Parameters Related To Relay Output - PR 9116 Manual Del Usuario

Convertidor universal
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Safety Manual

14.1.2 Parameters related to Relay Output

REL.UNI
REL.FUN
CONTAC.
SETP.
SETP.LO
SETP.HI
ACT.DIR
HYST
14
9116 UniverSal converter
Relay Units (for IN.TYPE ≠ TEMP):
PERC = Relay setpoint in percent of input range.
DISP = Relay setpoints and hysteresis values relates to DISP.LO
and DISP.HI (display units)
Relay Function:
OFF (Note 3 ) = Relay is always OFF
POW (Note 3 ) = Relay is always ON if power is applied
ERR = Relay is activated when sensor error is present
WIND = Relay is activated when input signal is between SETP.
LO and SETP.HI values
SETP = Relay is activated when input signal reaches SETP
value
Relay contact function:
N.C. = Normaly Closed relay contact (for REL.FUN = SETP)
N.O. = Normally Open relay contact (for REL.FUN = SETP)
O.I.W = Relay contact Open Inside Window (for REL.FUN =
WIND)
C.I.W = Relay contact Closed Inside Window (for REL.FUN =
WIND)
Relay setpoint value in REL.UNI units for IN.TYPE ≠ TEMP or
in UNIT for IN.TYPE = TEMP. (for REL.FUN = SETP)
Relay setpoint low value in REL.UNI units for IN.TYPE ≠ TEMP
or in UNIT for IN.TYPE = TEMP. (for REL.FUN = WIND)
Relay setpoint high value in REL.UNI units for IN.TYPE ≠ TEMP
or in UNIT for IN.TYPE = TEMP. (for REL.FUN = WIND)
Relay action for increasing or decreasing input signal
(for REL.FUN = SETP):
DECR = Relay activates when input signal ≤ SETP.
INCR = Relay activates when input signal ≥ SETP.
Hysteresis value in REL.UNI units for IN.TYPE ≠ TEMP or in
UNIT for IN.TYPE = TEMP. (for REL.FUN = SETP or WIND)
Version No. V3R0

Capítulos

Tabla de contenido
loading

Tabla de contenido