DST Summer Time
04
Yes Automatic switch between winter and summer
time activated by date
No No automatic switching to summer time
Airc: Interior Probe Calibration
05
Calibration must be carried out after 1 day of operation
with the same temperature setting as described below:
Place thermometer at a height of 1.5 m from the floor
(like the thermostat) and wait one hour to read actual
room temperature.
Enter calibration parameter; if "No" is displayed
(located on the right) it means that calibration has not
been performed.
Enter actual value shown by thermometer by pressing
(-) or (+). Press (OK) to validate.
Message "Yes" should be displayed; the value will be
saved in internal memory.
To delete the calibration made, press the Back key
(
).
Old value will be deleted and "No" will be displayed.
* Caution:
During all calibration steps, use only the heating
element controlled by the thermostat.
Amb.c: Exterior Space Probe Calibration
06
Calibrate in the same manner as described above if
exterior sensor is connected and used as exterior
space sensor.
flr.c: Floor Probe Calibration
If exterior sensor is used as floor sensor, the
thermometer should be located on the floor.
out.c: Exterior Space Probe Calibration
If exterior sensor is used to view outside sensor, use
outside thermometer for calibration.
* This parameter is only available in case external
probe is connected.
AFrz: Antifreeze temperature:
07
Antifreeze temperature is used in the Holiday mode.
Setting options: from 0.5 to 10.0°C; default value set to
7.0°C.