5. Charging algorithms
5.1. Intelligent charging algorithm for lead acid batteries
With optional reconditioning.
Charging voltages at room temperature:
MODE
NORMAL
HIGH
LI-ION
For 24V battery chargers: multiply all values by 2.
NORMAL (14.4V): recommended for wet-cell flat-plate lead-antimony batteries
(starter batteries), flat-plate gel and AGM batteries.
HIGH (14.7V): recommended for wet-cell lead-calcium batteries, Optima spiral
cell batteries and Odyssey batteries.
MODE button
Once the battery charger has been connected to the AC power supply, press the
MODE button to select a different charging algorithm if required (the battery
charger remembers the mode after disconnecting the power supply and/or
battery).
After selecting reconditioning, the RECONDITION LED will light up and start to
blink when reconditioning is active.
The battery charger switches to LOW (low power) when the MODE button is held
down for 3 seconds. The LOW LED will then remain lit. LOW mode will remain
active until the MODE button is held down for another 3 seconds.
ABS
FLOAT
STORAGE
V
V
V
14.4
13.8
13.2
14.7
13.8
13.2
14.2
13.5
13.5
9
RECONDITION
Max V@% of
Inom
16.2@8%, 1h
max
16.5@8%, 1h
max
N/A