Orbis DATA LOG Manual Del Usuario página 6

Interruptor horario
Idiomas disponibles

Idiomas disponibles

display. Press "OK " again and the display will show CLEAR C1 YES.
Use Δ and ∇ to choose between YES and NO and confirm pressing
"OK ". Press the " C " key repeatedly to go back to normal operating
mode.
12 (AM – PM) or 24-HOUR TIME MODE
You can choose between the time being displayed in AM : PM or 24-
hour format. In normal operating mode, press "OK " and use Δ and ∇ to
find EXTRAS 12/24H. From this menu, choose 12H or 24H and confirm
with "OK ". Press the " C " key repeatedly to return to normal operating
mode. If the 12h function has been chosen, AM or PM will be shown on
display, depending on the current time.
CYCLE PROGRAMMING
A cycle is a sequence of repetitive switches.
Each programmed cycle takes up two memory spaces (PROG X,
PROG X+1). Go into the MENU PROGRAM and press "OK ". Use the
Δ and ∇ keys to choose a program (PROG XX), press "OK " again and
PROG (XX) PROGRAM will be displayed. Confirm with "OK " and
C1:ON will be displayed. Select CYCLE, press "OK ", and you will see
DAY BEG MO: YES (to allow you to select the starting day for the
cycle). If you want it to begin on Monday, press "OK ", otherwise use the
Δ and ∇ keys until DAY BEG MO: NO appears on the display. Press
"OK " to accept and repeat the operation for the other days of the week,
selecting and confirming them in the same way.
When you have chosen the days, you need to select the start time for
the cycle, beginning with the hour. Use the Δ and ∇ keys to enter the
hour and confirm with "OK ". Enter the cycle start minutes in the same
way, and when you confirm "OK ", DAY END MO: YES (to allow you to
select the last day for the cycle) will be displayed. Repeat the same pro-
cedure to enter the days, hours and minutes for conclusion of the cycle.
Next, the cycle connection time (TIME ON ) needs to be programmed.
Enter the figures for hours and minutes (maximum 23 hours 59 minu-
tes.- minimum 0 hour 1 minute) and then the cycle disconnection time
(TIME OFF) in hours and minutes (maximum 23 hours 59 minutes.-
minimum 0 hour 1 minute). (See exemple )
Before programming, check that the next memory program is free. It is
it not free, option CYCLE will not then be available. CYCLE programs
are not permited in memory program 50. Do not program averlaped
cycles, as during the execution of one cycle, the overlaped cycle will not
start.
Cycles are shown in chronogram as ON from begining to the end.
Time ON
Time ON
Monday 9:00 h
2h20min. OFF
Begin day
Time OFF
TECHNICAL FEATURES
Power supply:
As indicated on the device
Switching capacity:
16 (10)A/250V
Maximum recomended loads:
Incandescent lamps.
Uncompensated fluorescent lamps. 1200 W.
Compensated fluorescent lamps.
Low- voltage halogen lamps.
Halogens (230 V.).
Low-consumption lamps-
Contact type and material:
Changeover AgSnO
Power consumption:
6 VA 1 circuit (approx.1 W)
Type of action:
1B, 1S, 1T, 1U
Number of programs:
50
Type of programs:
ON OFF
PULSE (1 to 59 seconds)
CYCLES (from 1 minute to 23 hours
59 minutes, in ON or OFF times)
Switching accuracy:
Better than 1 second
Operating accuracy:
≤ ± 1s/day at 23 °C
Reserve battery:
5 years. (Lithium Battery)
Working temperature:
-10 °C to +45 °C
Protection type:
IP 20 according to EN 60529
Protection class:
II according to EN 60335 when
mounting as intended
Pollution situation:
Normal
Sealable cover
LANGUAGE SELECTION
CLOCK SETTING
PROGRAMMING ON: Monday 09:10 OFF: Tuesday 11:30
Day end
Time OFF
Friday 13:00 h
DIMENSIONS
3000 W.
1200 W. 150 μF
1000 VA.
2500 W.
10X23 W.
2
PROGRAMMING CYCLE. START DAY: Monday 09:00. END DAY: Friday 18:00. ON: 2h OFF: 5h.
ORBIS TECNOLOGÍA ELÉCTRICA, S.A.
Lérida,61
E-28020 MADRID
http://www.orbis.es
A016.17.51249
Tel.: + 34 91 567 22 77
Fax: + 34 91 571 40 06