Error Codes
Error codes may be displayed if the controller or display case is malfunctioning. The
following is a list of error codes that may be encountered, and potential resolutions.
CODE DESCRIPTION
E0
Temperature
probe error
E1
Defrost probe
error
EE
Unit parameter
reading error
EF
Operating
parameter
reading error
Probe Temp
32° F (0° C)
77° F (25° C)
212° F (100° C)
Refrigerated Self-Serve Merchandiser (High Profile)
ERROR CODES AND RESOLUTIONS
CAUSE
Probe signal is
interrupted or
short-circuited
See E0
Operating
conditions
See EE
TEMPERATURE PROBE COMMON RESISTANCE CHART
Maximum
Resistance [ ]
1. Verify that probe wires and quick
disconnect are secure in control.
2. Check probe resistance to table
below. If 0 resistance is present
check wiring insulation. If infinite
resistance is present check for breaks
in wiring (meter will likely read
overload or very high in the mega-
ohm range).
3. Ensure that probes are wired per the
wiring diagram provided.
4. Replace probe if other remedies fail,
or if probe resistance deviates from
"Error! Reference source not
found." Error! Reference source
not found.
1. Remedy abnormal operating
conditions. The control is rated to
operate in a range of 14 to 122° F (-10
to 50° C) and less than 90%RH non-
condensing.
2. Replace control if problem persists.
Resistance [ ]
27.83
10.1
1
RESOLUTION
Normal
Resistance [ ]
27.28
10
0.97
Minimum
26.74
9.9
0.94
Page 17